3 Phase
Type of
outdoor
unit
Model Outdoor Units Input Current [A] Power Supply
Outdoor Unit Indoor Unit
Rated Voltage Range Outdoor (Down_Amp)
Indoor Total MCA MFA
Hz Volts Min. Max. Cooling Heating
A
AC100FCADGH AC100FB4DEH 50 380-415 342 456.5 12 12 0.7 12.7 12.7 15.0
RC100DHXGA
NS1004DXEA 50 380-415 342 456.5 12 12 0.7 12.7 12.7 15.0
NS100SDXEA 50 380-415 342 456.5 12 12 1.5 13.5 13.5 15.0
AC120HCADNH AC120HBMDKH 50/60 380-415 342 418 12 12 2.7 14.7 14.7 16.2
AC100HCADNH AC100HBMDKH 50/60 380-415 342 418 12 12 2.7 14.7 14.7 16.2
AC090HCADNH AC090HBMDKH 50/60 380-415 342 418 12 12 2.7 14.7 14.7 16.2
AC100JXADGH AC100JNCDEH 50 380-415 342 418 12 12 2.7 14.7 14.7 16.2
AC120JXADGH AC120JNCDEH 50 380-415 342 418 12 12 2.7 14.7 14.7 16.2
B
AC100FCAPGH AC100FB4PEH 50 380-415 342 456.5 12 12 1.0 13.0 13.0 15.0
RC100PHXGA NS1004PXEA 50 380-415 342 456.5 12 12 1.0 13.0 13.0 15.0
RC125DHXGA
NS1254DXEA 50 380-415 342 456.5 12 12 1.0 13.0 13.0 15.0
NS125SDXEA 50 380-415 342 456.5 12 12 2.0 14.0 14.0 15.4
RC125PHXGA NS1254PXEA 50 380-415 342 456.5 12 12 1.0 13.0 13.0 15.0
RC140DHXGA
NS1404DXEA 50 380-415 342 456.5 12 12 1.0 13.0 13.0 15.0
NS140SDXEA 50 380-415 342 456.5 12 12 2.0 14.0 14.0 15.4
AC140HCADNH AC140HBMDKH 50/60 380-415 342 418 12 12 2.7 14.7 14.7 16.2
AC140JXADGH AC140JNCDEH 50 380-415 342 418 12 12 2.7 14.7 14.7 16.2
C
RC140PHXGA NS1404PXEA 50 380-415 342 456.5 12 12 1.0 13.0 13.0 15.0
RC180DHXGH NS180HHXEH 50 380-415 342 456.5 12 12 2.9 14.9 14.9 16.4
RC180DHXGG NS180HHXEG 50 380-415 342 456.5 12 12 2.9 14.9 14.9 16.4
AC140HCAPNH AC140HBMPKH 50/60 380-415 342 418 12 12 2.7 14.7 14.7 16.2
AC120HCAPNH AC120HBMPKH 50/60 380-415 342 418 12 12 2.7 14.7 14.7 16.2
AC100HCAPNH AC100HBMPKH 50/60 380-415 342 418 12 12 2.7 14.7 14.7 16.2
1. Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above
listed range limits
2. Maximum allowable voltage variation between phases is 2%.
3. Wire size & type must comply with the applicable local and national code.
Wire size : Based on the value of MCA.
Wire type : 60245 IEC57(IEC) or H05RN-F(CENELEC) grade or more.
4. MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
5. MCA represents maximum input current.
MFA represents capacity which may accept MCA
Abbreviations
MCA : Min. Circuit Amps. (A)
MFA : Max. Fuse Amps. (A)
6. This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or
equal to Ssc(*2) at the interface point between the user’s supply and the public system. It is the responsibility
of the installer or user of the equipment to ensure, by consultation with the distribution network operator if
necessary, that the equipment is connected only to a supply with a short-circuit power Ssc greater than or
equal to Ssc(*2).
[Ssc (*2)]
Model Ssc[MVA] Model Ssc[MVA]
AC140HCAPKH 2.715 AC090HCADKH 2.954
AC140HCAPNH 2.074 AC090HCADNH 2.075
AC140HCADKH, AC140JXADEH 2.996 AC120HCAPKH 3.02
AC140HCADNH, AC140JXADGH 2.064 AC120HCAPNH 2.083
AC120HCADKH, AC120JXADEH 3.365 AC100HCAPKH 3.439
AC120HCADNH, AC120JXADEH 2.086 AC100HCAPNH 2.076
AC100HCADKH, AC100JXADEH, AC100JXADEH1 3.157 AC090HCAPKH 3.299
AC100HCADNH, AC100JXADGH 2.075 AC071HCAPKH 3.329