Samsung AC100KX4DKH/EU Manualul utilizatorului

Categorie
Aparate de aer condiționat cu sistem divizat
Tip
Manualul utilizatorului
Air conditioner
Installation manual
AC777KX4D7H
ŷ Thank you for purchasing this Samsung air conditioner.
ŷ Before operating this unit, please read this manual carefully and retain it for future
reference.
2 English
Contents
For information on Samsung’s environmental commitments and product-specific regulatory obligations, e.g. REACH,
WEEE, Batteries, visit : samsung.com/uk/aboutsamsung/samsungelectronics/corporatecitizenship/data_corner.html
Safety Information 3
General information 3
Installing the unit 4
Power supply line, fuse or circuit breaker 4
Installation Procedure 5
Step 1 Choosing the installation location 5
Step 2 Fixing the outdoor unit in place 7
Step 3 Connecting the power cables, communication cable, and controllers 8
Step 4 Optional: Extending the power cable 14
Step 5 Connecting the refrigerant pipe 16
Step 6 Optional: Cutting and flaring the pipes 17
Step 7 Installing oil traps 18
Step 8 Connecting up and removing air in the circuit 18
Step 9 Adding refrigerant (R-410A) 19
Step 10 Performing the gas leak test 21
Step 11 Connecting the drain hose to the outdoor unit 21
Step 12
Insulating the refrigerant pipes 22
Step 13 Checking the earthing 23
Step 14 Performing final check and trial operation 23
Extra procedures 27
Pumping down refrigerant 27
Relocating the indoor and outdoor units 27
Using the stop valve 27
Appendix 29
Troubleshooting 29
Technical specifications 31
COMMISSION DELEGATED REGULATION (EU) No 626/2011
i)
32
3English
Safety Information
WARNING
ŷ Hazards or unsafe practices that may result in severe
personal injury or death.
CAUTION
ŷ Hazards or unsafe practices that may result in minor
personal injury or property damage.
Carefully follow the precautions listed below because
they are essential to guarantee the safety of the
equipment.
WARNING
ŷ Always disconnect the air conditioner from the power
supply before servicing it or accessing its internal
components.
ŷ Verify that installation and testing operations are
performed by qualified personnel.
ŷ Verify that the air conditioner is not installed in an
easily accessible area.
General information
WARNING
ŷ Carefully read the content of this manual before
installing the air conditioner and store the manual in
a safe place in order to be able to use it as reference
after installation.
ŷ For maximum safety, installers should always
carefully read the following warnings.
ŷ Store the operation and installation manual in a safe
location and remember to hand it over to the new
owner if the air conditioner is sold or transferred.
ŷ This manual explains how to install an indoor unit
with a split system with two SAMSUNG units. The use
of other types of units with different control systems
may damage the units and invalidate the warranty.
The manufacturer shall not be responsible for
damages arising from the use of non compliant units.
ŷ This product has been determined to be in compliance
with the Low Voltage Directive (2006/95/EC), and the
Electromagnetic Compatibility Directive (2004/108/
EC) and the Machinery Directive (2006/42/EC) of the
European Union.
ŷ The manufacturer shall not be responsible for damage
originating from unauthorized changes or the
improper connection of electric and requirements set
forth in the “Operating limits” table, included in the
manual, shall immediately invalidate the warranty.
ŷ The air conditioner should be used only for the
applications for which it has been designed: the
indoor unit is not suitable to be installed in areas
used for laundry.
ŷ Do not use the units if damaged. If problems occur,
switch the unit off and disconnect it from the power
supply.
ŷ In order to prevent electric shocks, fires or injuries,
always stop the unit, disable the protection switch
and contact SAMSUNG’s technical support if the unit
produces smoke, if the power cable is hot or damaged
or if the unit is very noisy.
ŷ Always remember to inspect the unit, electric
connections, refrigerant tubes and protections
regularly. These operations should be performed by
qualified personnel only.
ŷ The unit contains moving parts, which should always
be kept out of the reach of children.
ŷ Do not attempt to repair, move, alter or reinstall the
unit. If performed by unauthorized personnel, these
operations may cause electric shocks or fires.
ŷ Do not place containers with liquids or other objects
on the unit.
ŷ All the materials used for the manufacture and
packaging of the air conditioner are recyclable.
ŷ The packing material and exhaust batteries of the
remote controller(optional) must be disposed of in
accordance with current laws.
ŷ The air conditioner contains a refrigerant that has
to be disposed of as special waste. At the end of its
life cycle, the air conditioner must be disposed of in
authorized centres or returned to the retailer so that
it can be disposed of correctly and safely.
Safety Information
4
Safety Information
English
Safety Information
ŷ This appliance is not intended for use by persons
(including children) with reduced physical, sensory
or mental capabilities, or lack of experience and
knowledge, unless they have been given supervision
or instruction concerning use of the appliance by a
person responsible for their safety. Children should
be supervised to ensure that they do not play with
the appliance.
ŷ For use in Europe: This appliance can be used by
children aged from 8 years and above and persons
with reduced physical, sensory or mental capabilities
or lack of experience and knowledge if they have
been given supervision or instruction concerning use
of the appliance in a safe way and understand the
hazards involved. Children shall not play with the
appliance. Cleaning and user maintenance shall not be
made by children without supervision.
Installing the unit
WARNING
IMPORTANT: When installing the unit, always remember
to connect first the refrigerant tubes, then the electrical
lines.
ŷ Upon receipt, inspect the product to verify that
it has not been damaged during transport. If the
product appears damaged, DO NOT INSTALL it and
immediately report the damage to the carrier or
retailer (if the installer or the authorized technician
has collected the material from the retailer.)
ŷ After completing the installation, always carry out a
functional test and provide the instructions on how to
operate the air conditioner to the user.
ŷ Do not use the air conditioner in environments with
hazardous substances or close to equipment that
release free flames to avoid the occurrence of fires,
explosions or injuries.
ŷ Our units should be installed in compliance with the
spaces shown in the installation manual, to ensure
accessibility from both sides and allow repairs
or maintenance operations to be carried out. The
unit’s components should be accessible and easy to
disassemble without endangering people and objects.
ŷ For this reason, when provisions of the installation
manual are not complied with, the cost required to
access and repair the units (in SAFETY CONDITIONS,
as set out in prevailing regulations) with harnesses,
ladders, scaffolding or any other elevation system
will NOT be considered part of the warranty and will
be charged to the end customer.
Power supply line, fuse or circuit
breaker
WARNING
ŷ Always make sure that the power supply is compliant
with current safety standards. Always install the air
conditioner in compliance with current local safety
standards.
ŷ Always verify that a suitable earthing connection is
available.
ŷ Verify that the voltage and frequency of the power
supply comply with the specifications and that the
installed power is sufficient to ensure the operation
of any other domestic appliance connected to the
same electric lines.
ŷ Always verify that the cut-off and protection switches
are suitably dimensioned.
ŷ Verify that the air conditioner is connected to the
power supply in accordance with the instructions
provided in the wiring diagram included in the
manual.
ŷ Always verify that electric connections (cable entry,
section of leads, protections…) are compliant with
the electric specifications and with the instructions
provided in the wiring scheme. Always verify that all
connections comply with the standards applicable to
the installation of air conditioners.
ŷ Devices disconnected from the power supply should
be completely disconnected in the condition of
overvoltage category.
ŷ Be sure not to perform power cable modification,
midway wiring, and multiple wire connection.
It may cause electric shock or fire due to poor
connection or insulation and current limit override.
When midway wiring is required due to power line
damage, refer to "Step 4 Optional: Extending the
power cable" in the installation manual.
5English
Installation Procedure
Installation Procedure
Step 1 Choosing the installation
location
Installation location requirements
ŷ Do not place the outdoor unit on its side or upside
down. Failing to do so may cause the compressor
lubrication oil to run into the cooling circuit and lead
to a serious damage to the unit.
ŷ Install the unit in a well-ventilated location away
from direct sunlight or strong winds.
ŷ Install the unit in a location that would not obstruct
any passageways or thoroughfares.
ŷ Install the unit in a location that would not
inconvenience or disturb your neighbors, as they
could be affected by the noise or the airflow coming
from the unit.
ŷ Install the unit in a location where the pipes and the
cables can be easily connected to the indoor unit.
ŷ Install the unit on a flat, stable surface that can
withstand the weight of the unit. Otherwise, the unit
can generate noise and vibration during operation.
ŷ Install the unit so that the air flow is directed towards
the open area.
ŷ Maintain sufficient clearance around the outdoor unit,
especially from a radio, computer, stereo system, etc.
Fuse
Fuse
Control
1.5 m or more
1 m or more
1 m or more
1.5 m or more
1.5 m or more
300 mm
Stereo
Computer etc
Outdoor Unit
200 mm
Air Guide Duct (This product is not provided by Samsung)
Indoor Unit
ŷ Install the unit at a height where its base can be
firmly fixed in place.
ŷ Make sure that the water dripping from the drain
hose runs away correctly and safely.
CAUTION
ŷ You have just purchased a system air conditioner
and it has been installed by your installation
specialist.
ŷ This device must be installed according to the
national electrical rules.
ŷ If your outdoor unit exceeds a net weight of 60 kg,
do not install it on a suspended wall, but stand it
on a floor.
ŷ When installing the outdoor unit at the seaside, make
sure that it is not directly exposed to sea breeze. If
you cannot find an adequate place free from direct
sea breeze, construct a protection wall or a protective
fence.
Install the outdoor unit in a place (such as near
buildings etc.) where it can be prevented from sea
breeze. Failure to do so may cause a damage to
the outdoor unit.
Sea breeze Sea breeze
Sea Sea
Outdoor Unit Outdoor Unit
ŷ If you cannot avoid installing the outdoor unit at the
seaside, construct a protection wall around to block
the sea breeze.
ŷ Construct a protection wall with a solid material such
as concrete to block the sea breeze. Make sure that
the height and the width of the wall are 1.5 times
larger than the size of the outdoor unit. Also, secure
a space larger than 700 mm between the protection
wall and the outdoor unit for exhausted air to
ventilate.
Protection wall
Outdoor Unit
Sea breeze
Sea
CAUTION
ŷ Depending on the condition of power supply, unstable
power or voltage may cause malfunction of the parts
or control system. (At the ship or places using power
supply from electric generator...etc)
6
Installation Procedure
English
Installation Procedure
ŷ Install the unit in a place where water can drain
smoothly.
ŷ If you have any difficulty finding installation location
as prescribed above, contact your manufacturer for
details.
ŷ Be sure to clean the sea water and the dust on the
heat exchanger of the outdoor unit and apply a
corrosion inhibitor on it. (At least once in a year.)
Outdoor unit dimensions
A Type
AC090KX4DKH/AC100KX4DKH/AC100KX4DNH/
AC120KX4DKH/AC120KX4DNH
998
977
537
528
620
9
4
0
330
384
360
675
B Type
AC140KX4DKH/AC140KX4DNH
620
330
384
360
1210
1185
940
567
558
675
C Type
AC071KX4DKH
880 53
310
660
364
18
798
Minimum clearances for the outdoor unit
When installing 1 outdoor unit
(Unit: mm)
300 or more
1500 or more
300 or
more
600 or
more
300 or
more
2000
or more
1500
or more
600
or more
300
or more
1500
or more
300 or
more
When installing more than 1 outdoor unit
(Unit: mm)
1500
or more
600
or more
3000
or more
3000
or more
300
or more
600
or more
600
or more
1500
or more
300
or more
1500
or more
600
or more
600
or more
300
or more
600
or more
600
or more
600
or more
300
or more
7English
Installation Procedure
300 or more
300 or more
500 or more 500 or more
CAUTION
ŷ The outdoor unit must be installed according to the
specified distances in order to permit accessibility
from each side, to guarantee correct operation,
maintenance, and repair of the unit.
The components of the outdoor unit must be
reachable and removable under safe conditions for
people and the unit.
WARNING
ŷ Should adopt bar type louver. Don’t use a type of rain
resistance louver.
[Bar type louver] [Rain resistance louver]
ŷ Louver specifications.
Angle criteria : less than 20°
Opening ratio criteria : greater than 80%
Moving the outdoor unit with wire rope
1 Before carrying the outdoor unit, fasten two wire
ropes of 8 m or longer, as shown in the figure.
2 To prevent damages or scratches effectively, insert
a piece of cloth between the outdoor unit and the
ropes.
3 Move the outdoor unit.
Wire rope
Plate protection
cloth
Step 2 Fixing the outdoor unit in place
Install the outdoor unit on a rigid and stable base to
prevent disturbance from any noise caused by vibration.
When installing the unit at a height or in a location
exposed to strong winds, fix the unit securely to a
support (i.e., a wall or a ground).
Fix the outdoor unit with anchor bolts. Make sure that
the anchor bolts are 20 mm or higher from the base
surface.
Anchor bolt hole
(Unit : mm)
(Unit : mm)
Anchor bolt hole
8
Installation Procedure
English
Installation Procedure
CAUTION
ŷ Install a drain outlet at the lowest end around the
base for outdoor unit drainage
ŷ When installing the outdoor unit on the roof,
waterproof the unit and check the ceiling strength.
ŷ Make sure that the wall can support the weights of
the rack and the outdoor unit.
ŷ Install the rack close to the column as much as
possible.
Optional: Fixing the outdoor unit to a wall with
a rack
Soft rubber designed to cut off vibration from
rack to wall. (not supplied with product)
Designed to cut off residual vibration from
outdoor unit to rack. (not supplied with product)
Anchor bolt
Base surface
20 mm
ŷ Install a proper grommet in order to reduce noise and
residual vibration transferred by the outdoor unit
towards the wall.
CAUTION
ŷ When installing an air guide duct, be sure to check
the following:
The screws do not damage the copper pipe.
The air guide duct is fixed firmly on the guard fan.
Step 3 Connecting the power cables,
communication cable, and controllers
You must connect the following three electrical cables to
the outdoor unit:
ŷ The main power cable between the auxiliary circuit
breaker and the outdoor unit.
ŷ The outdoor-to-indoor power cable between the
outdoor unit and the indoor unit.
ŷ The communication cable between the outdoor unit
and the indoor unit.
CAUTION
ŷ During installation, make first the refrigerant
connections and then the electrical connections. If
the unit is uninstalled, first disconnect the electrical
cables and then the refrigerant connections.
ŷ Connect the air conditioner to the earthing system
before making the electrical connections.
NOTE
ŷ Especially, if your outdoor unit is the one designed
for Russian and European markets, consult the supply
authority, if necessary, to estimate and reduce the
supply system impedance before installation.
Air conditioning system examples
When using earth leakage circuit breaker (ELCB) for a
single phase
MCCB
ELCB
ELB
Main power
cable
Communication cable
Outdoor-to-indoor power cable
Earthing
Outdoor Unit
OR
Indoor Unit
9English
Installation Procedure
When using earth leakage circuit breaker (ELCB) for a
3-phase, 4-wire system (3P4W)
MCCB
ELCB
ELB
Main power
cable
Communication cable
Outdoor-to-indoor power cable
Earthing
Outdoor Unit Indoor Unit
OR
CAUTION
ŷ If the outdoor unit is installed in a location vulnerable
to an electric leak or submergence, make sure to
install an ELCB.
Connecting the main power cable
When using ELB for 1 phase and 3 phase
1(L) 2(N) L1(R) L2(S) L3(T) N
F1 F2
1(L) 2(N) L N
F1 F2
MCCB
MCCB
ELB
Power supply
Electrical
component box
The appearance of the unit may be
different from the picture depending
on the model.
Indoor Unit
1-phase
3-phase
Main power
cable
Communication cable
Communication
cable
3-phase 4-wire
main power cable
(AC 380V)
Outdoor-to-
indoor power
cable
Outdoor-to-
indoor power
cable
Cable tie
Cable tie
10
Installation Procedure
English
Installation Procedure
CAUTION
ŷ You should connect the power cable into the power
cable terminal and fasten it with a clamp.
ŷ The unbalanced power must be maintained within 2%
of supply rating.
If the power is unbalanced greatly, it may shorten
the life of the condenser. If the unbalanced power
is exceeded over 4% of supply rating, the indoor
unit is protected, stopped and the error mode
indicates.
ŷ To protect the product from water and possible shock,
you should keep the power cable and the connection
cord of the indoor and outdoor units within ducts.
(with appropriate IP rating and material selection for
your application)
ŷ Ensure that main supply connection is made through
a switch that disconnects all poles, with contact gap
of a least 3 mm.
ŷ Devices disconnected from the power supply should
be completely disconnected in the condition of
overvoltage category.
ŷ Keep distances of 50 mm or more between power
cable and communication cable.
Main power terminal block specifications
1-phase terminal block specifications 3-phase terminal block specifications
1(L) 2(N) L N
AC power (AC071KX4DKH):
M4 screw
1(L) 2(N) L N
AC power
(AC090/100/120/140KX4DKH) :
M5 screw
1(L) 2(N) L1(R) L2(S) L3(T) N
AC power :
M5 screw
9.95 11.55
Communication:
M4 screw
F1 F2
Communication:
M4 screw
F1 F2
Main power cable specifications
The power cable is not supplied with air conditioner.
ŷ Select the power supply cable in accordance with relevant local and national regulations.
ŷ Wire size must comply with the applicable local and national code.
ŷ Specifications for local wiring power cord and branch wiring are in compliance with local cord.
Single phase
Type
Model Outdoor unit Input current (Amperes) Power supply
Indoor unit Outdoor unit
Rated
Voltage range
Outdoor unit
Indoor
unit
Total MCA MFA
Hz Volts Min
.
Max
.
Cooling Heating
A
AC090KN4DKH/EU
AC090KX4DKH/EU
50 220 to 240 198 264 23 23 1.5 24.5 24.5 26.95
AC100KN4DKH/EU
AC100KX4DKH/EU
50 220 to 240 198 264 23 23 1.5 24.5 24.5 26.95
AC120KN4DKH/EU
AC120KX4DKH/EU
50 220 to 240 198 264 25 25 1.5 26.5 26.5 29.15
B
AC140KN4DKH/EU
AC140KX4DKH/EU
50 220 to 240 198 264 32 32 1.5 33.5 33.5 36.85
C
AC071KN4DKH/EU
AC071KX4DKH/EU
50 220 to 240 198 264 20 20 1.5 21.5 21.5 23.65
11English
Installation Procedure
3-phase
Type
Model Outdoor unit Input current (Amperes) Power supply
Indoor unit Outdoor unit
Rated
Voltage range
Outdoor unit
Indoor
unit
Total MCA MFA
Hz Volts Min
.
Max
.
Cooling Heating
A
AC100KN4DKH/EU
AC100KX4DNH/EU
50 380 to 415 342 456.5 16.1 16.1 1.5 17.6 17.6 17.6
AC120KN4DKH/EU
AC120KX4DNH/EU
50 380 to 415 342 456.5 16.1 16.1 1.5 17.6 17.6 17.6
B
AC140KN4DKH/EU
AC140KX4DNH/EU
50 380 to 415 342 456.5 16.1 16.1 1.5 17.6 17.6 17.6
NOTE
1 Voltage range
ŷ Units are suitable for use on electrical systems
where voltage supplied to unit terminal is not
below or above listed range limits
2 Maximum allowable voltage variation between
phases is 2%.
3 Wire size & type must comply with the applicable
local and national code.
ŷ Wire size: Based on the value of MCA.
ŷ Wire type: 60245 IEC57(IEC) or H05RN-
F(CENELEC) grade or more.
4 MFA is used to select the circuit breaker and the
ground fault circuit interrupter (earth leakage circuit
breaker).
5 MCA represents maximum input current.
ŷ MFA represents capacity which may accept MCA
ŷ Abbreviations
MCA: Min. Circuit Amps. (A)
MFA: Max. Fuse Amps. (A)
6 This equipment complies with IEC 61000-3-12
provided that the short-circuit power Ssc is greater
than or equal to Ssc (*2) at the interface point
between the user’s supply and the public system.
It is the responsibility of the installer or user of
the equipment to ensure, by consultation with the
distribution network operator if necessary, that the
equipment is connected only to a supply with a short-
circuit power Ssc greater than or equal to Ssc(*2).
Model Ssc[MVA]
AC071KX4DKH/EU 1.48
AC090KX4DKH/EU 3.14
AC100KX4DKH/EU 3.14
AC100KX4DNH/EU 2.70
AC120KX4DKH/EU 1.08
AC120KX4DNH/EU 2.98
AC140KX4DKH/EU 2.97
AC140KX4DNH/EU 3.03
Silence mode controller wiring diagram
(AC090/100/120/140KX4D*H)
Outdoor unit
ASSY Control out
Non-voltage contact
12
Installation Procedure
English
Installation Procedure
Connecting the outdoor-to-indoor power cable
and the communication cable
1-phase
LN
F1 F2
1(L) 2(N) L N
F1 F2
Outdoor-to-indoor
power cable
For connecting the power and
communication cables
Main power cable Communication cable
Cable tie
Indoor Unit
Outdoor Unit
3-phase
LN
F1 F2
1(L) 2(N) L1(R) L2(S) L3(T) N
F1 F2
Indoor Unit
Outdoor-to-indoor
power cable
3-phase 4-wire main
power cable (AC 380V)
Communication
cable
Cable tie
Outdoor Unit
NOTE
ŷ Lay the electrical wiring so that the front cover does
not rise up when doing wiring work and attach the
front cover securely.
ŷ Ground wire for the indoor unit and outdoor unit
connection cable must be clamped to a soft copper
tin-plated eyelet terminal with M4 screw hole(NOT
SUPPLIED WITH UNIT ACCESSORIES).
Outdoor-to-indoor power terminal
specifications
ŷ Connect the cables to the terminal board using the
compressed ring terminal.
ŷ Cover a solderless ring terminal and a connector part
of the power cable and then connect it.
Silver solder
13English
Installation Procedure
Nominal
dimensions
for cable
(mm²)
Nominal
dimensions
for screw
(mm)
BDd1EFLd2t
Standard
dimension
(mm)
Allowance
(mm)
Standard
dimension
(mm)
Allowance
(mm)
Standard
dimension
(mm)
Allowance
(mm)
Min.
(mm)
Min.
(mm)
Max.
(mm)
Standard
dimension
(mm)
Allowance
(mm)
Min.
(mm)
4/6
4 9.5
±0.2 5.6
+0.3
-0.2
3.4 ±0.2 6
5 20 4.3
+0.2
0
0.9
815 9 28.5 8.4
+0.4
0
10 8 15 ±0.2 7.1
+0.3
-0.2
4.5 ±0.2 7.9 9 30 8.4
+0.4
0
1.15
16 8 16 ±0.2 9
+0.3
-0.2
5.8 ±0.2 9.5 13 33 8.4
+0.4
0
1.45
25
812
±0.3 11.5
+0.5
-0.2
7.7 ±0.2 11
15
34
8.4
+0.4
0
1.7
8 16.5 13 8.4
35
816
±0.3 13.3
+0.5
-0.2
9.4 ±0.2 12.5
13 38 8.4
+0.4
0
1.8
822 13 43 8.4
50 8 22 ±0.3 13.5
+0.5
-0.2
11.4 ±0.3 17.5 14 50 8.4
+ 0.4
0
1.8
70 8 24 ±0.4 17.5
+0.5
-0.4
13.3 ±0.4 18.5 20 51 8.4
+ 0.4
0
2.0
ŷ Connect the rated cables only.
ŷ Connect using a driver which is able to apply the
rated torque to the screws.
ŷ If the terminal is loose, fire may occur caused by arc.
If the terminal is connected too firmly, the terminal
may be damaged.
7LJKWHQLQJWRUTXHNJIŷFP
M4 12.0 to 18.0
M5 20.0 to 30.0
ŷ 1N · m = 10 kgf · cm
CAUTION
ŷ When connecting cables, you can connect the cables
to the electrical part or connect them through the
holes below depending on the spot.
ŷ Connect the communication cable between the
indoor and outdoor units through a conduit to protect
against external forces, and feed the conduit through
the wall together with refrigerant piping.
ŷ Remove all burrs at the edge of the knock-out hole
and secure the cable to the outdoor knock-out using
lining and bushing with an electrical insulation such
as rubber and so on.
ŷ Must keep the cable in a protection tube.
ŷ Keep distances of 50mm or more between power
cable and communication cable.
ŷ When the cables are connected through the hole,
remove the Plate bottom.
14
Installation Procedure
English
Installation Procedure
Outdoor-to-indoor power and communication
cables specifications
Indoor power supply
Power supply Max/Min (V) Indoor power cable
1ĭ, 220-240V,
50 Hz
±10% 2.5 mm²
Ĺ
, 3 wires
Communication cable
0.75 to 1.5 mm², 2 wires
ŷ Power supply cords of parts of appliances for
outdoor use shall not be lighter than polychloroprene
sheathed flexible cord. (Code designation IEC:60245
IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC 66 /
CENELEC: H07RN-F)
ŷ When installing the indoor unit in a computer room
or net work room, use the double shielded (tape
aluminium / polyester braid + copper ) cable of
FROHH2R type.
Step 4 Optional: Extending the power
cable
1 Prepare the following tools.
Tools Spec Shape
Crimping pliers MH-14
Connection sleeve
(mm)
20 x Ø6.5
(HxOD)
Insulation tape
Width 19
mm
Contraction tube
(mm)
70 x Ø8.0
(LxOD)
2 As shown in the figure, peel off the shields from the
rubber and wire of the power cable.
ŷ Peel off 20 mm of cable shields from the pre-
installed tube.
CAUTION
ŷ For information about the power cable specifications
for indoor and outdoor units, refer to the installation
manual.
ŷ After peeling off cable wires from the pre-installed
tube, insert a contraction tube
Power cable
Pre-installed tube for the power cable
(Unit: mm)
(Unit: mm)
20 20
20
20
60
120
180
3 Insert both sides of core wire of the power cable into
the connection sleeve.
ŷ Method 1: Push the core wire into the sleeve from
both sides.
ŷ Method 2: Twist the wire cores together and push
it into the sleeve.
Connection sleeve Connection sleeve
Method 1 Method 2
4 Using a crimping tool, compress the two points and flip it
over and compress another two points in the same location.
ŷ The compression dimension should be 8.0.
Compression
dimension
15English
Installation Procedure
ŷ After compressing it, pull both sides of the wire to
make sure it is firmly pressed.
Compress it 4 times.
5 mm
Compress it 4 times.
5 mm
Method 1 Method 2
5 Wrap it with the insulation tape twice or more and
position your contraction tube in the middle of the
insulation tape.
Three or more layers of insulation are required.
Method 1 Method 2
Insulation tape
40 mm
35 mm
Insulation tape
6 Apply heat to the contraction tube to contract it.
Contraction tube
7 After tube contraction work is completed, wrap it with
the insulation tape to finish.
Insulation tape
CAUTION
ŷ Make sure that the connection parts are not exposed
to outside.
ŷ Be sure to use insulation tape and a contraction tube
made of approved reinforced insulating materials that
have the same level of withstand voltage with the power
cable. (Comply with the local regulations on extensions.)
WARNING
ŷ In case of extending the electric wire, please DO NOT
use a round-shaped pressing socket.
Incomplete wire connections can cause electric
shock or a fire.
16
Installation Procedure
English
Installation Procedure
Step 5 Connecting the refrigerant pipe
Items Maximum allowable length
Outdoor unit
models
AC071KX4DKH
AC090KX4DKH
AC100KX4DKH
AC100KX4DNH
AC120KX4DKH
AC120KX4DNH
AC140KX4DKH
AC140KX4DNH
Main pipe (L1) 50 m 75 m
Max. height
difference
between outdoor
and indoor units
(h1)
30 m 30 m
L
1
h
1
n=1
indoor
Outdoor
ŷ Temper grade and minimum thickness of the
refrigerant pipe
Outer diameter
[mm]
Minimum
thickness [mm]
Temper grade
ø6.35 0.7
C1220T-O
ø9.52 0.7
ø12.70 0.8
ø15.88 1.0
ø15.88 0.8
C1220T-1/2H OR
C1220T-H
ø19.05 0.9
ø22.23 0.9
CAUTION
ŷ Be sure to use C1220T-1/2H (Semi-hard) pipe for
more than Ø19.05 mm. If you use C1220T-O (Soft)
pipe for Ø19.05 mm, the pipe may be broken, which
can result in an injury.
Make at least one round:
It will reduce noise and vibration
ŷ The appearance of the unit may be different from the
diagram depending on the model.
17English
Installation Procedure
CAUTION
ŷ After connecting the pipes with knock-out treatment,
plug the space around the pipes.
ŷ After connecting the pipes, proceed exactly as
directed in the guide to prevent interference with the
internal parts.
Step 6 Optional: Cutting and aring the
pipes
1 Make sure that you have the required tools available.
(pipe cutter, reamer, flaring tool, and pipe holder)
2 If you wish to shorten the pipes, cut it with a pipe
cutter, taking care to ensure that the cut edge remains
at a 90° angle with the side of the pipe. Refer to
the illustrations below for examples of edges cut
correctly and incorrectly.
90°
Oblique
Rough Burr
3 To prevent any gas from leaking out, remove all burrs
at the cut edge of the pipe, using a reamer.
4 Slide a flare nut on to the pipe and modify the flare.
D
A
D
45° ±2°
90° ±2°
Pipe
Flare
Flare
R 0.4 to 0.8 mm
L
Outer diameter (D) Depth (A) Flare dimension (L)
ø6.35 mm 14 to 18 8.7 to 9.1 mm
ø9.52 mm 34 to 42 12.8 to 13.2 mm
ø12.70 mm 49 to 61 16.2 to 16.6 mm
ø15.88 mm 68 to 82 19.3 to 19.7 mm
ø19.05 mm 100 to 120 23.6 to 24.0 mm
ŷ 1 N·m = 10 kgf·cm
5 Check that the flaring is correct, referring to the
illustrations below for examples of incorrect flaring.
Correct Inclined Damaged
Surface
Cracked Uneven
Thickness
CAUTION
ŷ If the pipes require brazing ensure that OFN(Oxygen
Free Nitrogen) is flowing through the system.
ŷ Nitrogen blowing pressure range is 0.02 to 0.05 MPa.
18
Installation Procedure
English
Installation Procedure
Step 7 Installing oil traps
Check the following list and install an oil trap.
ŷ Based on cooling operation, install it on the gas side
pipe only.
ŷ Install the oil trap only in between the outdoor unit
and the first branch joint and it should be installed at
every 10 m.
ŷ Radius of curvature (R) on the oil trap are as follows;
Pipe
diameter
(D)
12.70 15.88 19.05 22.23 25.40 28.60 31.75
Radius of
curvature
(R)
25 and
over
32 and
over
38 and
over
41 and
over
51 and
over
57 and
over
60 and
over
ŷ Height of the oil trap (H): 4R ≤ H ≤ 6R
ŷ When the indoor unit is installed at a higher place
than the outdoor unit
H
R
Outdoor Unit
Indoor Unit
Oil trap (Install it
at every 10 m)
Step 8 Connecting up and removing air
in the circuit
CAUTION
ŷ When installing, make sure there is no leakage. When
recovering the refrigerant, ground the compressor
first before removing the connection pipe. If the
refrigerant pipe is not properly connected and the
compressor works with the service valve open, the
pipe inhales the air and it makes the pressure inside
of the refrigerant cycle abnormally high. It may cause
explosion and injury.
The air in the indoor unit and in the pipe must be
evacuated. If air remains in the refrigerant pipes, it will
affect the compressor either reduce cooling/heating
capacity or lead to a malfunction. Refrigerant for air
purging is not charged in the outdoor unit. Use Vacuum
Pump as shown at the right figure.
1 Connect each assembly pipe to the appropriate valve
on the outdoor unit and tighten the flare nut.
2 Referring to the illustration below, tighten the flare
nut on section D first manually and then with a
torque wrench, applying the following torque.
Outdoor Unit
A (Gas)
B (Liquid)
D
C
3 Connect the charging hose of low pressure side of
manifold gauge to the packed valve having a service
port as shown at the figure.
CAUTION
ŷ The designs and shape are subject to change
according to the model.
Outer Diameter (D) 7RUTXH1ŷP
ø6.35 14 to 18
ø9.52 34 to 42
ø12.70 49 to 61
ø15.88 68 to 82
ø19.05 100 to 120
19English
Installation Procedure
4 Open the valve of the low pressure side(A) of
manifold gauge anticlockwise.
A(Gas)
B(liquid)
Outdoor Unit
Vacuum
Pump
5 Purge the air from the system using vacuum pump
for about 10 minutes.
ŷ Close the valve of the low pressure side of
manifold gauge clockwise.
ŷ Make sure that pressure gauge shows -0.1 MPa
(-76 cmHg) after about 10 minutes. This procedure
is very important to avoid a gas leak.
ŷ Turn off the vacuum pump.
ŷ Remove the hose of the low pressure side of
manifold gauge.
6 Open the stop valve of both liquid and gas sides.
7 Mount the valve stem nuts and the service port
cap to the valve, and tighten them at the torque of
NJIŷFPZLWKDWRUTXHZUHQFK
8 Check for gas leakage.
ŷ At this time, especially check for gas leakage from
the 3-way valve’s stem nuts(A port), and from the
service port cap.
CAUTION
ŷ Connect the indoor and outdoor units using pipes
with flared connections (not supplied). For the lines,
use insulated, unwelded, degreased and deoxidized
copper pipe, (Cu DHP type to ISO 1337 or UNI EN
12735-1), suitable for operating pressures of at least
4200 kPa and for a burst pressure of at least 20700
kPa. Copper pipe for hydro-sanitary applications is
completely unsuitable.
ŷ For sizing and limits (height difference, line length,
max. bends, refrigerant charge, etc.) see “Connecting
refrigerant pipe section”.
Step 9 Adding refrigerant (R-410A)
ŷ The outdoor unit is loaded with sufficient refrigerant
for the standard piping. Thus, refrigerant must be
added if the piping is lengthened. This operation
can only be performed by a qualified refrigeration
specialist. To determine the quantity of refrigerant
charge, see Calculating the quantity of refrigerant to
add on page 20.
1 Check if the stop valve is closed completely.
2 Charge the refrigerant through the service port of the
liquid stop valve.
NOTE
ŷ Do not charge the refrigerant through the service
port of the gas stop valve.
3 If you have any difficulty charging the refrigerant as
described in the steps above, take the following steps:
a Open the liquid stop valve and gas stop valve.
b Operate the air conditioner by pressing the K2
key on the outdoor unit PCB.
c After about 30 minutes, charge the refrigerant
through the service port of the gas stop valve.
20
Installation Procedure
English
Installation Procedure
Indoor Unit
Outdoor Unit
Liquid side stop valve(service port)
Gas side stop valve(service port)
Balance
Ref
Vacuum
pump
Important information regulation regarding the
refrigerant used
This product contains fluorinated greenhouse gases. Do
not vent gases into the atmosphere.
CAUTION
ŷ Inform user if system contains 5 tCOe or more of
fluorinated greenhouse gases. In this case, it has to be
checked for leakage at least once every 12 months,
according to regulation n°517/2014. This activity has
to be covered by qualified personnel only.
ŷ In case situation above (5 tCOe or more of
R-410A), installer (or recognized person which
has responsibility for final check) has to provide a
maintenance book, with all the information recorded
according to REGULATION (EU) No 517/2014 OF THE
EUROPEAN PARLIAMENT AND OF THE COUNCIL of 16
April 2014 on fluorinated greenhouse gases.
Please fill in the following with indelible ink on the
refrigerant charge label supplied with this product and
on this manual.
ŷ
: The factory refrigerant charge of the product.
ŷ
: The additional refrigerant amount charged in the
field.
ŷ
+ : The total refrigerant charge.
Indoor Unit
Outdoor Unit
Unit kg tCOe
, a
, b
+ , c
Refrigerant type GWP value
R-410A 2088
ŷ GWP: Global Warming Potential
ŷ Calculating tCOe : kg x GWP / 1000
NOTE
a Factory refrigerant charge of the product: see unit
name plate
b Additional refrigerant amount charged in the
field(Refer to the above information for the
quantity of refrigerant replenishment.)
c Total refrigerant charge
d Refrigerant cylinder and manifold for charging
Calculating the quantity of refrigerant to add
The quantity of additional refrigerant is variable
according to the installation situation. Thus, make sure
the outdoor unit situation before adding refrigerant.
This operation can only be performed by a qualified
refrigeration specialist.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48

Samsung AC100KX4DKH/EU Manualul utilizatorului

Categorie
Aparate de aer condiționat cu sistem divizat
Tip
Manualul utilizatorului

în alte limbi