Mark PinTherm Connect Technical Manual

Tip
Technical Manual
Technical manual
Technisches Handbuch
Livret technique
Technisch boek
Instrukcja techniczna
Manuel tehnic
EN
DE
FR
NL
PL
MARK PinTherm CONNECT
0664047
RO
OK
RESET
ESC
0
I
PinTherm Connect
06.29.108
MON
DAY
08:01
X:060
18ºC
06 29 108
2
Read this document before
installing the appliance
Warning
Incorrect installation, adjustment, alteration, repair or maintenance work may lead to material
damage or injury. All work must be carried out by certied, qualied professionals. If the
appliance is not positioned in accordance with the instructions, the warranty shall be rendered
void. This appliance is not intended for use by children or persons with a physical, sensory or
mental handicap, or who lack the required experience or expertise, unless they are supervised
or have been instructed in the use of the appliance by somebody who is responsible for their
safety. Children must be supervised to ensure that they do not play with the appliance.
EN
3
1.0 Contents
2.0 General
2.1 All rights reserved page 4
2.2 General warnings page 4
3.0 Technicalspecications
3.1 Technical specications PinTherm Connect page 4
3.2 Technical specications external room sensor (optional) page 5
3.3 Resistance chart room sensor (optional) page 5
3.4 Default settings PinTherm Connect page 5
4.0 Installation
4.1 General page 6
4.2 Installation PinTherm Connect page 6
4.3 Installation external room sensor page 6
5.0 Operating manual
5.1 Explanation of the push-buttons and LEDs page 7
5.2 Explanation of the display page 8
5.3 Initial operation of the PinTherm Connect page 8
5.4 Activate user menu page 9
5.5 Enter or change switching times page 9
5.6 Change day/night temperature setting page 10
5.7 Change time and date page 10
5.8 Vacation settings page 10
5.9 Change menu code page 10
5.10 Change language page 11
5.11 Calibration temperature page 11
5.12 Heating/Cooling page 11
5.13 Switching difference page 12
5.14 Changing minimum control signal page 12
5.15 Changing maximum control signal page 12
5.16 Change control signal range page 12
5.17 Modbus page 13
5.18 Ethernet info page 13
5.19 IP settings page 13
5.20 Switch overtime timer on/off page 13
5.21 Switch on chimney-sweep function page 14
5.22 Restore factory settings PinTherm Connect page 14
6.0 Disposing of the PinTherm Connect page 14
7.0 Modbus page 14
8.0 PinTherm Connect connections page 15
Annex I Wiring diagrams page 87
Annex II Modbus page 94
4
2.0 General
2.1 All rights reserved
The manufacturer has a policy of continuous product improvement and reserves the right to
make changes to the specications without prior notice. The technical details are considered
correct but do not form the basis for a contract or warranty. All orders are accepted subject to
the standard terms and conditions of sale and delivery (which will be sent to you at your request).
2.2 General warnings
Installation must comply with the relevant local and/or national regulations. You must therefore
have the PinTherm Connect installed by a professionally qualied installer in accordance with
all applicable national and international regulations. Faulty installation, adjustment, alteration,
maintenance activity or repair shall render the warranty void.
Always switch off the 230V power supply before connecting the terminals. The mains voltage
on the PinTherm Connect must be able to be switched off in a double-pole manner by means
of a permanent switch that is suitable for 250VAC / 10A and complies with the applicable safety
regulations.
Only devices that comply with EN-IEC 61010-1 may be operated with the PinTherm Connect.
Clean the housing of the PinTherm Connect with a damp cloth. Do not apply solvents.
There are no requirements regarding ventilation in the immediate vicinity of the controller.
Warning - risk of electric shock.
Warning - general warning, risk of danger.
There can be voltage on the connection terminals where a is placed.
3.0 Technicalspecications
3.1 Technical specications PinTherm Connect
Type designation : PinTherm Connect
Item number : 06 29 108
Power supply PinTherm Connect : 90 – 240 VAC / 47-63Hz
Own consumption : < 9W
Clock : 24 hour clock with automatic summer/winter time switching
Switching programs : 3 switching programs a day
Switching differential : 0,1 - 3K
Dimensions : 166 x 160 x 106mm (bxwxh)
Weight : 880 grammes
Protection class : IP-54
Installation environment : Transport/storage: -20°C until +70°C.
Operational: -10°C until +60°C
Relative air humidity: 0-90% not condensating
Installation maximal 2000 meter above sea level.
Over voltage category : 11
Pollution level : 2
Switch contact(s)* : Heating: 230Vac/16A (4A)
Others: 230Vac/10A (2,5A)
Temperature setting : 0 until 39°C per 1°C adjustable
Overtime timer : adjustable 1, 2 or 3 hours (060, 120, 180)
!
!
EN
5
Calibration : adjustable from -3.5°C until +3.5°C
Heating/cooling : Reversible contact for heating or cooling
0-10 VDC : 0-10 VDC output for heating or cooling
Sensor : external room sensor (06 29 086)
Languages : NL/EN/DE/FR/PL/RO/LT
Fuse : 6A
* The relay contacts are functional switches, not safety switches.
3.2 Technical details external room sensor (optional)
Type designation : RSTF NTC4,7K
Item number : 06 29 086
Resistance : NTC 4K7
Dimensions : 79 x 81 x 26mm (lxwxh)
Weight : 46 grammes
Electrical connection : 0.75 -1.5mm²
Protection class : IP-30
3.3 Resistance chart room sensor (optional)
-15°C -10°C -5°C 0°C 5°C 10°C 15°C
32.937kΩ 25.217kΩ 19.392kΩ 15.040kΩ 11.743kΩ 9.241kΩ 7.330kΩ
20°C 25°C 30°C 35°C 40°C 45°C 50°C
5.855kΩ 4.700kΩ 3.777kΩ 3.071kΩ 2.512kΩ 2.066kΩ 1.709kΩ
3.4 Default settings PinTherm Connect
Menu code : 1000
Switching times : MA, DI, WO, DO, VR 07:30-17:30 hours
ZA, ZO 00:00-00:00 hours
Room temperature : Day setting 18°C
Night setting 08°C
Calibration temp. : +0.0
Switching difference : 1K
Heating/cooling : Heating
0-10V range : 1K
0-10V min : 0V
0-10V max : 10V
Modbus : Slave ID 001
IP-setting : static
6
4.0 Installation
4.1 General
After unpacking, check the PinTherm Connect and the external room sensor (if applicable) for
damage. Check that the type/model and the rated voltage are correct.
4.2 Installation PinTherm Connect
Determine a suitable place for installing the PinTherm Connect. Mount the PinTherm Connect
on a solid surface that can carry a minimum of 4 kg. We recommend mounting the PinTherm
Connect at a height of ±1.5m from the oor, at a well reachable place.
For cable gland use only cable glands tted with strain relief, with a minimum re class of UL94V2.
Check that the power supply has been switched off before connecting any wiring. If this is not the
case, the power supply must be switched off before you continue. When switching off the power
supply of the appliance to which connection is to be made, you should also refer to the technical
documentation/operating instructions for the appliance in question.
Connect the PinTherm Connect according to one of the supplied electrical diagrams which are in
the back of this technical book. To select the correct connection diagram, you need to know on
which type of device you will connect the PinTherm Connect. For a selection see also Annex I.
When applying a 0-10VDC signal, see the table below for the correct cable diameter and
associated length.
Diameter Length
0.8mm
2
80 meter
1.0mm
2
100 meter In this case, we advise the use of a shielded cable.
1.5mm
2
150 meter
4.3 Installation external room sensor
Place the external room sensor draft-free, in view of the appliance at a height of approx. 1.5m
from the oor. And connect the sensor to the appropriate terminals in the PinTherm Connect.
Refer to the chart below for the correct wire diameter and length.
Diameter Length
0.8mm
2
80 meter
1.0mm
2
100 meter In this case, we advise the use of a shielded cable.
1.5mm
2
150 meter
EN
7
5.0 Operating manual
5.1 Explanation of the push-buttons and LEDs
A - Illuminated display (see also 5.2)
B - Push-button for switching the heating mode on and off.
C - LED, lit when the heating mode is active.
D - Push-button for switching the continuous ventilation mode on and off.
E - LED, lit when the continuous ventilation mode is active.
F - Push-button for switching the appliance out of lock-out after a (burner) fault.
G - LED, lit when a (burner) fault has been detected.
H - Push-button for activating the user menu or to display the next value.
I - Push-button for conrming a selection/change or for displaying the next menu item.
J - Push-button for exiting the setting or menu without executing a change.
K - Push-button for switching the overtime timer on and off.
L - Push-button + – to change a setting.
M - LED, lit when there is heat demand in the heating mode (burner on).
N - LED, lit when the fan is switched on.
O - LED, lit when the overtime timer function is active.
C
OK
PinTherm Connect
06.29.108
MON
DAY
08:01
E
G
M
N
O
D
F
J K LI
A
B
H
RESET
ESC
0
I
18ºC
X:060
8
5.2 Explanation of the display
A - Indicates the day of the week.
B - The current clock time is shown here.
C - Indicates the measured temperature (°C).
D - Indicates the number of minutes before the overtime timer function is switched off again and
the PinTherm Connect will return to night temperature control mode.
E - Indicates whether the PinTherm Connect is set to daytime mode (DAY) or to night mode
(NIGHT) and temperature control based on the daytime or night temperature setting.
5.3 Initial operation of the PinTherm Connect
When you connect a power supply to the PinTherm Connect for the rst time, you will be asked
to select your choice of language (language settings: NL, EN, DE, FR, PL, RO, LT). Having done
so, the next step is to set the time and date. After the time and date have been set, the PinTherm
Connect displays the main screen.
Language options: NL, EN, DE, FR, PL, RO, LT
C
MA
DAG
08:01
E
D
B
A
18ºC
X:060
SELECT LANGUAGE SAT 01-01-2006
00:00:00
16°CMON
DAY
08:00
changes the
ashing digit
to go one digit up
select the desired
language
OK OK
ENGLISH
EN
9
5.4 Activate user menu
You can change the following settings in the menu:
Enter/change switching times
Change day/night setting
Change time/date
Vacation settings
Change menu code
Change language
Calibration
0-10V min 0-5V
0-10V max 5-10V
0-10V range (1-3)
Modbus
IP settings
5.5 Enter or change switching times
ENTER MENU CODE
leave the menu and go back
to the main screen
Default setting Menu
code
1000
°CMON
DAY
08:01
changes the flashing
digit
to go one digit up
make your menu choice
with these buttons
ESC
OK OK
0000
SET/CHANGE
PROGRAM
MONDAY
etc.
back to the
menu
changes the
flashing digit
to go up one digit
OK
OK
OK
07:30 -> 17:00
SET/CHANGE
PROGRAM
MONDAY
OK
--:-- -> --:--
changes the
flashing digit
to go up one digit
OK
12
MONDAY
--:-- -> --:--
3 TUESDAY
07:30 -> 17:00
1 SUNDAY
--:-- -> --:--
3
10
5.6 Change day/night temperature setting
5.7 Change time and date
5.8 Vacation settings
During the set time block, the control will regulate according to the night temperature.
5.9 Change menu code
VACATION ACTIVE
ON
back to the
menu
select
select
on or off
OK OK
VACATION SETTING
FROM: 01-07-2017
TILL: 01-08-2017
OK
changes the
flashing light
to go up one digit
18°C
DAY SETTING
NIGHT SETTING
select
back to the
menu
changes the
flashing digit
to go one digit up
changes the
flashing digit
to go one digit up
OK OK
OK
08°C
SET/CHANGE
TEMPERATURE
MON 23-03-2009
09:10:00
back to the
menu
select
changes the
flashing digit
to go one digit up
OK OK
CHANGE
TIME/DATE
1000
CHANGE MENU CODE
SELECT NEW CODE
New menu code
back to the
menu
select
changes the
flashing digit
to go one digit up
OK OK
EN
11
5.10 Change language
Language options: NL, EN, DE, FR, PL, RO, LT.
5.11 Calibration temperature
If the external room sensor is installed in an unfavourable position, the actual temperature and the
temperature measured by the PinTherm Connect may differ. This temperature difference can be
compensated by setting a correction factor in this temperature calibration function.
For example: The measured temperature is 18°C, but the PinTherm Connect display
indicates 20°C. The difference in this example is 2°C too high.
The correction value must be set to -2°C.
5.12 Heating/Cooling
Setting to make the controller suitable for controlling heating or cooling.
HEATING/COOLING
HEATING
back to
the menu
select
change setting
OK
HEATING/COOLING
OK
ENGLISH
SELECT LANGUAGE
back to the
menu
select the desired
language
select
OK OK
CHANGE LANGUAGE
CALIB. TEMP. CALIB. TEMP.
Correctionvalue is adjustable
back to the
menu
select
changes the
flashing digit
to go one digit up
OK OK
+ 0.0°C
from -3,5°C to +3,5°C
12
5.13 Switching difference
Adjustable between 0.1 and 3.0 K.
5.14 Change minimum control signal
Note:
When there is no demand for heat, the PinTherm Connect sends out a signal of 0VDC.
5.15 Change maximum control signal
5.16 Change control signal range
This function determines when the 0 – 10VDC signal is modulated back in conditions of heat
demand. When set to 1.0, the PinTherm Connect will start to modulate the 0 - 10V signal at 1K
below the target temperature.
The range can be set between 0.5 – 3.0 and is set to 1.0 as standard.
SWITCHING DIFF.
1.0K
back to
the menu
select
changes the
flashing digit
OK
SWITCHING DIFF.
OK
select
change setting
OK OK
0-10V min(0-5V)
2.0 V
0-10V min(0-5V)
back to
the menu
select
change setting
OK OK
0-10V max(5-10V)
10.0 V
0-10V max(5-10V)
back to
the menu
back to
the menu
select
change setting
OK OK
0-10V Range(1-3)
1.0
0-10V Range(1-3)
EN
13
5.17 ModBus
Slave ID: adjustable 1 - 247
Factory setting: 1
5.18 Ethernet Info
Display set IP address.
5.19 IP settings
DHCP - automatic assignment IP address
Static - set xed IP address
SUBnet Mask
5.20 Switch overtime timer on/off
This function provides the option of manually switching to the daytime temperature outside the
set switching times for a period of 1, 2 or 3 hours.
The yellow LED with the symbol is lit when this function is active. In addition, the bottom
right of the display shows the time in minutes that still remains before the function is deactivated
and the PinTherm Connect returns to night temperature control. The function can also be swit-
ched off prematurely by pressing the push-button again until the yellow LED extinguishes and the
number of remaining minutes disappears from the display.
IP ADDRESS
192.168.001.100
back to the
menu
select
OK OK
ETHERNET INFO
MAC ADDRESS
5410EC220037
OK
IP MODE
STATIQ
back to the
menu
select
OK OK
IP SETTINGS
IP ADDRESS
192.168.001.100
OK
change setting
changes the
flashing digit
to go one digit up
SUBNET MASK
255.255.255.000
changes the
flashing digit
to go one digit up
MODBUS SETTINGS
001
back to the
menu
select
changes the
flashing digit
OK
MODBUS SETTINGS
OK
to go one digit up
14
See the illustration below.
5.21 Switch on chimney-sweep function
You can use this function to switch the appliance temporarily to full heat output/partial heat
output so that measurements can be taken. Refer to the information below for instructions on
how to switch this function on and off. After activation, this function remains switched on for 15
minutes and will switch off automatically again after that period.
5.22 Restore factory settings PinTherm Connect
All the factory settings are restored when you activate this function. This function may be
activated at any time. See the illustration below.
6.0 Disposing of the PinTherm Connect
When the PinTherm Connect is replaced or removed, it must be recycled or destroyed in
accordance with national and/or local legislation and regulations.
7.0 Modbus
- Communication [12]
- Modbus-list [13]
NIGHT
MON
X:060
18°C
MON
DAY
17:01
X:120
MON
DAY
17:01
X:180
MON
DAY
17:01
17:01
18°C
18°C
18°C
This switches the function o and takes you back
to the main screen
ESC
0-10V
10V
14:59
press to increase the voltage (maximum of 10V)
Use the push-buttons referred to below to have the
appliance run at a lower voltage (reduce the heat output)
press to lower the voltage
Press and hold down
for ±12 seconds
0
keep pressed or
+/- 12 secs
SELECT LANGUAGE
16°CMON
DAY
08:01
This will return you to the
screen from which you
selected this function and
default settings will not be
restored.
OK OK
ESC
ENGLISH
DEFAULT SETTINGS
RESTORED!
RESET TO DEFAULT
SETTINGS?
EN
15
8.0 PinTherm Connect connections
L N Connection terminals (230Vac/50Hz)
21 - 22 Continuous ventilation
21 - 23 Heating/cooling
24 - 25 Fault signal
25 - 26 Reset
+ - 0-10Vdc (Heating/cooling)
11 - 12 External room sensor
A - B MODBUS RTU (R ground)
RJ 45 connector Internet / Modbus TCP/IP
13 - 14 Contact external fan
Warning: Dangerous voltage present on N, L, 13, 14, 21, 22, 23, 24, 25 and 26
With the PinTherm Connect, only devices that comply with the safety regulations as laid down in
EN-IEC 61010-1 may be controlled.
PinTherm Connect
06.29.108
MON
DAY
08:01 18ºC
X:060
OK
RESET
ESC
0
I
16
Lesen Sie dieses Dokument sorgfältig
durch, bevor Sie das Gerät installieren
Warnhinweis
Fehlerhaft durchgeführte Installationen, Einstellungen, Änderungen, Reparaturen oder
Wartungsmaßnahmen können zu Sachschäden und Verletzungen führen. Alle Arbeiten
müssen von geprüften, qualizierten Fachleuten durchgeführt werden. Falls das Gerät nicht
vorschriftsgemäß aufgestellt wird, erlischt die Garantie. Dieses Gerät ist nicht für den Gebrauch
durch Personen (einschließlich Kindern) mit verminderter körperlicher, Sinnes- oder geistiger
Leistungsfähigkeit oder mangelnder Erfahrung und mangelnden Kenntnissen bestimmt, sofern sie
nicht unter Aufsicht stehen oder durch eine Person, die für ihre Sicherheit verantwortlich ist, im
Gebrauch des Geräts angeleitet werden. Kinder müssen vom Gerät ferngehalten werden.
17
DE
1.0 Inhalt
2.0 Allgemeines
2.1 Änderungen vorbehalten Seite 18
2.2 Allgemeine Warnhinweise Seite 18
3.0 Technische Daten
3.1 Technische Daten PinTherm Connect Seite 18
3.2 Technische Daten externer Raumfühler (optional) Seite 19
3.3 Widerstandstabelle (externer) Raumfühler Seite 19
3.4 Werkseinstellungen PinTherm Connect Seite 19
4.0 Montage
4.1 Allgemeines Seite 20
4.2 Montage PinTherm Connect Seite 20
4.3 Montage eines externen Raumfühlers (optional) Seite 20
5.0 Bedienungsanleitung
5.1 Erläuterung der Drucktasten und LEDs Seite 21
5.2 Erläuterung des Displays Seite 22
5.3 Erste Inbetriebnahme der PinTherm Connect Seite 22
5.4 Aktivierung des Benutzermenüs Seite 23
5.5 Schaltzeiten eingeben oder ändern Seite 23
5.6 Tages- und Nachttemperatur ändern Seite 24
5.7 Uhrzeit und Datum ändern Seite 24
5.8 Einstellung der Urlaubsreglung Seite 24
5.9 Menücode ändern Seite 24
5.10 Sprachauswahl ändern Seite 25
5.11 Justierung Seite 25
5.12 Heizen / Kühlen Seite 25
5.13 Schaltdifferenz Seite 26
5.14 Minimumregelsignal ändern Seite 26
5.15 Maximumregelsignal ändern Seite 26
5.16 Bereich Minimumregelsignal ändern Seite 26
5.17 Modbus Seite 27
5.18 Ethernet Info Seite 27
5.19 IP-Einstellungen Seite 27
5.20 Überstundenzähler ein-/ausschalten Seite 27
5.21 Schornsteinfegerfunktion einschalten Seite 28
5.22 Werkseinstellungen der PinTherm Connect wiederherstellen Seite 28
6.0 Entsorgung der PinTherm Connect Seite 28
7.0 Modbus Seite 28
8.0 Anschlussmöglichkeiten der PinTherm Connect Seite 29
Anhang I Anschlussschema Seite 87
Anhang II Modbus Seite 94
18
2.0 Allgemeines
2.1 Änderungen vorbehalten
Der Hersteller strebt eine kontinuierliche Verbesserung der Produkte an und behält sich das
Recht vor, ohne vorherige Mitteilung, Änderungen an den technischen Daten vorzunehmen.
Die technischen Angaben werden als korrekt angenommen, bilden aber keine Grundlage
für einen Vertrag oder Gewährleistungsansprüche. Alle Bestellungen werden gemäß den
Standardkonditionen in unseren allgemeinen Verkaufs- und Lieferbedingungen angenommen (diese
werden auf Anfrage zur Verfügung gestellt).
2.2 Allgemeine Warnhinweise
Die Installation muss den geltenden landesweiten und örtlichen Bestimmungen entsprechen.
Daher darf das Gerät nur von einem sachkundigen und qualizierten Installateur unter Beachtung
der nationalen und internationalen Vorschriften installiert werden. Im Falle einer unsachgemäßen
Installation, Einstellung, Änderung, Wartung oder Instandsetzung erlischt die Gewährleistung.
Vor dem Aufschrauben der Klemmen immer die 230V-Stromversorgung ausschalten. Die
Netzspannung am PinTherm Connect muss durch einen permanenten Schalter, der für 250VAC /
10A geeignet ist und die geltenden Sicherheitsvorschriften erfüllt, zweipolig abgeschaltet werden
können.
Nur Geräte, die EN-IEC 61010-1 entsprechen, dürfen mit dem PinTherm Connect betrieben
werden.
Reinigen Sie das Gehäuse des PinTherm Connect mit einem feuchten Tuch. Keine Lösungsmittel
auftragen.
Es gibt keine Anforderungen an die Belüftung in unmittelbarer Nähe des Reglers.
Warnung - Gefahr eines Stromschlags.
Warnung - Allgemeine Warnung
Die Stromanschlüsse können an den Anschlussklemmen vorgenommen werden, an denen sich
einer
!
bendet.
3.0 Technische Daten
3.1 Technische Daten PinTherm Connect
Typbezeichnung : PinTherm Connect
Artikelnummer : 06 29 108
Spannungsversorgung : 90 – 240 VAC / 47-63Hz
Eigenverbrauch : < 9W
Uhr : 24 Std. Uhr mit automatischer Umstellung auf Sommer und
Winterzeit
Schaltprogramm : 3 Schaltprogramme pro Tag
Schaltdifferenz : 0,1 - 3K
Größe : 166 x 160 x 106mm (LxBxH)
Gewicht : 880 Gramm
Schutzart : IP54
Installationsumgebung : Transport / Lagerung: -20 ° C bis + 70 ° C
Betrieb: -10 ° C bis + 60 ° C
Relative Luftfeuchtigkeit: 0-90% nicht kondensierend
Installation maximal 2000 Meter über dem Meeresspiegel.
!
19
DE
Überspannungskategorie : 11
Verschmutzungsgrad : 2
Schaltkontakt:* : Heizung: 230Vac/16A (4A)
Andere: 230Vac/10A (2,5A)
Temperatureinstellung : 0 bis 39 °C pro 1°C einstellbar
Überstunden-Timer : einstellbar 1, 2 oder 3 Stunden (060,120,180)
Kalibrierung : einstellbar von -3,5 ° C bis + 3,5 ° C
Heizen /Kühlen : Umschaltkontakt zum Heizen oder Kühlen
0-10 VDC : 0-10 VDC Ausgang zum Heizen oder Kühlen
Fühler : externer Raumfühler (06 29 086)
Einstellbare Sprachen : NL/EN/DE/FR/PL/RO/LT
Vorsicherung : 6A
* Die Relaiskontakte sind Funktionsschalter, keine Sicherheitsschalter.
3.2 Technische Daten externer Raumfühler (optional)
Typbezeichnung : RSTF NTC4,7K
Artikelnummer : 06 29 086
Widerstand : NTC 4K7
Abmessungen : 79 x 81 x 26mm (L x B x H)
Gewicht : 46 Gramm
Elektrischer Anschluss : 0.75 -1.5mm²
Schutzgrad : IP-30
3.3 Widerstandstabelle (externer) Raumfühler
-15°C -10°C -5°C 0°C 5°C 10°C 15°C
32.937kΩ 25.217kΩ 19.392kΩ 15.040kΩ 11.743kΩ 9.241kΩ 7.330kΩ
20°C 25°C 30°C 35°C 40°C 45°C 50°C
5.855kΩ 4.700kΩ 3.777kΩ 3.071kΩ 2.512kΩ 2.066kΩ 1.709kΩ
3.4 Werkseinstellungen PinTherm Connect
Menücode : 1000
Schaltzeiten : MA, DI, WO, DO, VR 07:30-17:30 Uhr
ZA, ZO 00:00-00:00 Uhr
Raumtemperatur : Tagestemperatur 18°C
Nachttemperatur 08°C
Justierung : +0.0
Schaltdifferenz : 1K
Heizen / Kühlen : Heizen
0-10V range : 1K
0-10V min : 0V
0-10V max : 10V
Modbus : Slave ID 001
IP-Einstellungen : statisch
20
4.0 Montage
4.1 Allgemeines
Prüfen Sie nach dem auspacken der PinTherm Connect und - falls bestellt - den mitgelieferten
externen Raumfühler auf Beschädigungen. Überprüfen Sie die Richtigkeit des gelieferten Typs/
Models sowie die elektrische Spannung.
4.2 Montage des PinTherm Connect
Legen Sie einen geeigneten Ort für den Einbau der PinTherm Connect fest. Montieren Sie den
PinTherm Connect auf einer Oberäche, die mindestens 4kg tragen kann. Es wird empfohlen, die
PinTherm Connect auf ± 1,5 m über dem Fußboden anzubringen, an einem leicht zugänglichen
Ort.
Verwenden Sie für die Kabeleinführung nur Kabelverschraubungen mit einen Zugentlastung
der Mindestbrandklasse UL94V2. Stellen Sie sicher, dass die Stromversorgung ausgeschaltet
ist, bevor Sie ein Kabel anschließen. Sollte dies nicht der Fall sein, muss die Stromversorgung
ausgeschaltet werden. Beziehen Sie vor dem Ausschalten der Stromversorgung auf die jeweilige
Bedienungsanleitung des Gerätes.
Schließen Sie den PinTherm Connect gemäß einem der mitgelieferten Schaltpläne an. Diese
nden Sie auf der Rückseite des technischen Handbuchs. Um das richtige Verbindungsdiagramm
auszuwählen, müssen Sie wissen, an welchem Gerätetyp Sie den PinTherm Connect anschließen.
Für eine Auswahl siehe auch Anhang I.
Wenn ein 0-10VDC-Signal angelegt wird, Siehe nachfolgende Tabelle für den richtigen
Kabeldurchmesser und die richtige Länge.
Durchmesser Länge
0.8mm
2
80 m
1.0mm
2
100 m Es wird empfohlen, hierfür ein geschirmtes Kabel zu
1.5mm
2
150 m verwenden.
4.3 Montage eines externen Raumfühlers (optional)
Platzieren Sie den externen Raumfühler geschützt in Sichtweite des Gerätes in einer Höhe von ca.
1,5 Meter, gemessen ab dem Boden. Schließen Sie den Sensor an die entsprechenden Klemmen
im PinTherm Connect an. Siehe nachfolgende Tabelle für den richtigen Kabeldurchmesser und die
richtige Länge.
Durchmesser Länge
0.8mm
2
80 m
1.0mm
2
100 m Es wird empfohlen, hierfür ein geschirmtes Kabel zu
1.5mm
2
150 m verwenden.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100

Mark PinTherm Connect Technical Manual

Tip
Technical Manual