Aqua-Scope PRELWE02 LoRaWAN Pressure Monitor Manual de utilizare

Tip
Manual de utilizare
LoRaWAN Pressure
Monitor
SKU: PRELWE02
Version: 2.0.0
Product Description
The Aqua-Scope pressure sensor records the temperature and pressure of the water. The device consists
of two parts:
Main housing for signal processing and radio communication with battery compartment.
The external sensor head is connected to the water pipe. The stainless steel sensor head has a
silicon sensor mounted in silicone oil for highly accurate and low-noise pressure measurements in
a wide operating range. The measuring range for pressure is between 1 and 10 bar. The sensor
values are converted into digital values directly in the measuring head to suppress interference
from the connection to the main housing. In addition, the temperature of the liquid medium is
measured directly at the stainless steel diaphragm and is therefore very precise.
The sensor can send an alarm message if freely definable threshold values are exceeded or not reached.
The sensor's polling frequency can be set between 0.1 second and several minutes and defines the
battery life. For a measuring interval of 1 second, a battery life of approx. 10 years is calculated.
The device communicates via LoRaWAN as a Class A device and can also be operated as a Class C
device via configuration parameters.
The device is powered either via an external power supply with USB-C power supply unit or via an
optional internal ER26500 battery (Bobbin Cell C).
Both the sensor head (IP67) and the main housing (IP65) are waterproof and can be used outdoors or in
particularly humid and/or dirty environments.
Installation
Users and Installation Manual: LoRaWAN Pressure Monitor (PRELWE02)
Copyright © 2022 Aqua-Scope Technologies, Sakala tn 7-2, 10141 Tallinn, Estonia, www.aqua-scope.com
The sensor head is screwed into inspection openings of existing
water pipes or other suitable locations via a ¼ inch thread. If no
inspection opening is available it is possible to use the edge
valve below a sink or beside a toilet. For this option the
installation is described below.
To make it short and easy – the video on aqua-scope.com/install
explains the installation of the Aqua-Scope Sensor Head step by
step:
1. In case there are two edge valves under the sink, please
identify the cold-water supply. Just open hot water and
check which valve warms up.
2. Close the faucet and close the edge valve by turning
clockwise.
3. Remove the metal hose from the edge valve using the 19
mm wrench supplied. You may want to have a towel on
hand to catch the water leaking from the end of the hose.
4. Mount the T-shaped connector on top of the edge valve
and fasten it using the 19 mm wrench.
5. Connect the metal hose to the upper end of the connector
and fasten it using the 19 mm wrench.
6. Screw the Aqua-Scope pressure sensor head into the side
opening of the connector and fasten it by hand. There is no need to make it super-tide.
7. Re-Open the edge valve by turning the knob anti-clockwise.
8. Please check all three connections for some seconds that there are no leaks.
9. Attach the Aqua-Scope to a suitable location using double-side tape and plug the sensor head into
the water-proof screwable terminal of the main device. Attach the wired flood sensor to the small
round terminal if desired.
10. Power the device using the USB C Power Plug. Please use the power supply provided within the
scope of delivery. This power supply has very low distortion factor required for precise
measurements of pressure.
Reset to Factory Default State
The factory default state is indicated by the LEDs blinking green/red. Please push the button after the
initial buzzer beep (but not earlier!) and keep it pushed for 5 seconds. After 5 seconds you hear a low-
frequency sound. Now release the button! This reset sequence will delete all settings including network
access credentials.
Pairing with the LoRaWAN Network
Please register the device with its three keys with your LoRaWAN server before commissioning. You will
find the Device EUI printed on the device. Enter this key plus your registered email address on
https://aqua-scope.com/lora to obtain the missing keys. The email address is the account email from
Users and Installation Manual: LoRaWAN Pressure Monitor (PRELWE02)
Copyright © 2022 Aqua-Scope Technologies, Sakala tn 7-2, 10141 Tallinn, Estonia, www.aqua-scope.com
Aqua-Scope Shop purchases or the data is provided by your Point of Sale.
Functions and Usage
Every 15 minutes (when mains powered) or every hour (when battery operated) the device reports the
following sensor values:
Pressure of the water,
Temperature of the water right at the sensor head.
The sensor values can be accessed in the Aqua-Scope App or they are reported into the network when
integrated into third party systems. The device offers a low watermark and a high watermark threshold
that can be defined using the mobile app. If the valued are exceeded an under pressure or overpressure
alarm is issued.
Beside the water-related alarms the device also reports certain device-related conditions as alarm:
No external sensor head connected
Head present but no contact to water
Battery Low
Mains Power lost
Bad communication network quality
All these alarm conditions are monitored continuously. Alarms are indicated on the device with red LED
and buzzer sound (both can be disabled in the app) and they are reported into the Aqua-Scope Cloud
and shown in the Aqua-Scop App. If the alarm condition disappears the alarm is reversed but will remain
in green color in the app for information. Swiping them in the apps home page finally deleted them.
Further alarm reactions such as email, push notification or even a voice call can be defined in the Aqua-
Scope App.
LoRaWAN Payload Commands (Payload Format)
LoRaWAN commands can be daisy chained into the payload up to the defined maximum payload size of
51 bytes. This mean that for all commands sent to defined number of bytes in the payload is required to
avoid misinterpretation of command and/or command values in the receiver side. All uplink and
downlink commands use FPort=10.
Uplink Command Hardware Version Report: 0x03 - HW - CAP_MSB CAP_LSB (4 Byte): This
command reports the hardware version and a bitmap of the capabilities of the device. It is sent
Users and Installation Manual: LoRaWAN Pressure Monitor (PRELWE02)
Copyright © 2022 Aqua-Scope Technologies, Sakala tn 7-2, 10141 Tallinn, Estonia, www.aqua-scope.com
unsolicited as the first command during boot-up and as replying command to downlink command
Hardware Version Get. HW is a single byte indicating the version of the hardware. The bitmap
indicates the different capabilities of the device.
Uplink Command Configuration Report: 0x04 - IDX - VAL_MSB - VAL_LSB (4 Byte): This
command reports a configuration parameter of the device: IDX is the number of the configuration
parameter. The 16 Bit VAL is the parameter itself. Configuration parameters are always 16 Bit
values. The table below describes the configuration parameters and their values.
Uplink Command Sensor Report: 0x06 - ID - VAL_MSB - VAL_LSB (4 Byte): This command
reports sensor values. The ID indicates the sensor type and defines the format of the 16-Bit VAL.
The sensor types of this devices are listed below.
Uplink Command Firmware Version Report: 0x0a - VER_MSB VER_2 VER_3 VER LSB (5
Byte): This command reports the 32-bit value of the current firmware. It is sent unsolicited as the
first command during boot-up and as replying command to downlink command 'Hardware Version
Get'.
Uplink Command Alarm Report: 0x0b - STATE - TYPE - VAL_MSB - VAL_LSB (5 Byte): This
command reports start and end of alarms. The STATE-Byte indicates the status of the alarm (0x01
= active, 0x00 = inactive). The TYPE Byte indicates the type of alarm and defines the content of
the 16 Bit VAL. Possible alarm IDs and the values reported are listed below.
Uplink Command Battery Report: 0x12 - VOLT - BAT_MSB - BAT_LSB (4 Byte): This
command reports the status of the battery. VOLT is the measured voltage of the battery in 100 mV
steps, the BAT value is the consumption of the current battery - as counted inside the system - in
mAh.
Downlink Command System Command: 0x01 - CMD (2 Byte): This command sends a system
command to the devices. CMD defines the type of command:
CMD = 0x01: System restart
CMD = 0x02: System Reset - back to factory default
Downlink Command Hardware Version Get: 0x03 - (1 Byte): This command calls for a
Hardware Version Report sent upstream
Downlink Command Configuration Set: 0x04 - IDX - VAL_MSB - VAL_LSB (4 Byte): This
command allows setting configuration parameters of the device: IDX is the number of the
configuration parameter. The 16 Bit VAL is the parameter itself. Configuration parameters are
always 16 Bit Values. The table below describes the configuration parameters and its values.
Downlink Command Sensor Get: 0x06 - ID (2 Byte): This command requests the report of
sensor values. The ID indicates the sensor type. The sensor types of the devices are listed below.
Downlink Command Alarm Clear: 0x0b - TYPE (2 Byte): This command clears an alarm. TYPE
is the type of alarm to be cleared. Type = 0 clears all active alarms. For other types of alarms to
be cleared please refer to the uplink command 0x0b.
Downlink Command Configuration Get: 0x14 - IDX (2 Byte): This command allows reading
the configuration value IDX. The device will respond with an upstream command Configuration
Report
LoRaWAN Sensor Types
The following sensor types are supported by the Aqua-Scope Monitor.
Users and Installation Manual: LoRaWAN Pressure Monitor (PRELWE02)
Copyright © 2022 Aqua-Scope Technologies, Sakala tn 7-2, 10141 Tallinn, Estonia, www.aqua-scope.com
0x01: Temperature: VAL is temperature in 1/10 Degree Celsius, (2-complement). Example: 0x06
0x01 0x00 0xCD => Temperature 0x00CD = 205 = 20.5 C., 0x06 0x01 0xFF 0xEA =>
Temperature 0xFFEA = -20 = -2 C
0x03: Uptime: VAL is the number of hours after last boot
0x10: Water Pressure: VAL is unsigned water pressure in mBar. Example: 0x10 0x011 0x0D 0x48
=> Pressure 0x0D48 = 3400 = 3.4 Bar.
LoRaWAN Alarm Types
The following alarmtypes are supported by the Aqua-Scope Monitor.
0x0001 (Bit 00) : All Alarms
0x0002 (Bit 01) : Flood Sensor Tripped, VAL is 0x01 or 0x00.
0x0004 (Bit 02) : Freeze/Frost Danger, VAL is actual temperature.
0x0010 (Bit 04) : Water Underpressure, Value is actual water pressure.
0x0040 (Bit 06) : Water Overpressure.Value is actual water pressure.
0x1000 (Bit 12) : Battery Low.
0x2000 (Bit 13) : Lost Mains Power.
0x4000 (Bit 14) : Sensor Head Not Connected
0x8000 (Bit 15) : Sensor Head not in contact with water.
LoRaWAN Configuration Parameters
All Configuration Parameters are 2 Byte values that can be set and read out using LoRaWAN
'Configuration Get' and 'Configuration Set' commands. Here is an overview of the configuration
parameters currently used:
Parameter 1 (0x01): System Register (Default: 0x5bfe = dec 23550)
The bitmap defines the general behavior of the device. Bit = 1 means function enabled, bit = 0 means
function disabled.
0x0001 (Bit 00) : Main Processor in Sleep Mode
0x0002 (Bit 01) : LORAWAN communication
0x0004 (Bit 02) : Wifi communication
0x0008 (Bit 03) : Serial communication
0x0020 (Bit 05) : Buzzer active
0x0040 (Bit 06) : LED active
0x0400 (Bit 10) : n.n.
0x0800 (Bit 11) : high frequency (1) versus low frequency(0)
0x1000 (Bit 12) : base operation interval msb
0x2000 (Bit 13) : base operation interval
0x4000 (Bit 14) : base operation interval
0x8000 (Bit 15) : base operation interval lsb
When High-Frequency Bit set to 1: 4 MSB defines interval in 2 * ms from 2 -32 ms (val 1 - 16).
When High-Frequency Bit set to 0: 4 MSB defines interval as 125 ms power of x, ranging from x = 1 =
Users and Installation Manual: LoRaWAN Pressure Monitor (PRELWE02)
Copyright © 2022 Aqua-Scope Technologies, Sakala tn 7-2, 10141 Tallinn, Estonia, www.aqua-scope.com
125 ms to x = 14 = 2048 sec = 34 min , x=15 is not allowed.
Parameter 6 (0x06): Over-Pressure Alarmthreshold (Default: 0x1f40 = dec 8000)
An overpressure alarm is sent as an uplink message when the current pressure exceeds this threshold.
The threshold value is automatically set 24 hours after initial setup during calibration and may change
from time to time as a result of ongoing calibration. The value is accepted in mBar.
Parameter 7 (0x07): Under-Pressure Alarm threshold (Default: 0x07d0 = dec 2000)
A heavy flow alarm is sent as an uplink message when the current pressure falls below this threshold for
a certain time. The threshold value is automatically set 24 hours after initial setup during calibration and
may change from time to time as a result of ongoing calibration. The value is accepted in mBar.
Parameter 19 (0x13): Alarm Enable/Disable (Default: 0xd806 = dec 55302)
The bitmap defines which alarm type is active and will cause an alarm status command 0x0b. Bit = 1
means function enabled, bit = 0 disables the function. The different alarm types are shown in the section
'LoRaWAN Alarm Types'.
Parameter 29 (0x1d): Reporting Interval (Default: 0x0384 = dec 900)
This parameter defines the interval in seconds the device automatically reports sensor values and
heartbeat as an uplink message.
LED-Signals
All colors blinking: device boots up
Yellow blinking: Devices tries to connect to network
Red fast blinking (mains powered) or steady: Alarm
green/red blinking: factory default
3 times green blinking plus buzzer: Device connected to network successfully and is ready to work
Blue glowing (mains powered) or all LEDs off (battery operated): Device is operating
Battery Operation
If the device is battery-operated all focus in on extending battery life. The battery life depends on
several factors:
Presence of a Pressure Reduction Valve: If a PRV is present the device will draw significantly less
power and the battery life extends at least by a factor of 2.
Interval of status reporting. In mains power mode the device will report its status every 20 seconds
and receive commands from the app/Cloud. In battery mode the device wakes up every hour only.
Hence, every command such as open/close of the valve or setting certain parameters will be
executed with delay.
All status data such as temperature of water, consumption etc. are only reported once per hour (in
mains every 15 minutes)
The stand-by animation of blue led glowing is turned off in battery mode.
Users and Installation Manual: LoRaWAN Pressure Monitor (PRELWE02)
Copyright © 2022 Aqua-Scope Technologies, Sakala tn 7-2, 10141 Tallinn, Estonia, www.aqua-scope.com
You find an estimation of the battery lifetime in the app under ‘Devices’. With PRV the battery will last
about 8…10 years, without PRV the lifetime is about 4 years.
Scope of Delivery
Water Monitor main device (without battery)
Pressure sensor head with 80 cm cable
3/8 Inch water pipe connector (T-shaped)
One external flood sensor with cable
USB-C power cable and power supply
19 mm wrench to unfasten and fasten the 3/8 Inch connections of the pipe connector
Manual
Information related to Drinking Water Directive EU 98/83/EC
The t-shaped part of the device is exposed to drinking water and therefore subject to the European
Drinking Water Directive. The certified used material is called CW509L, which is in the list of approved of
materials of the German Environment Agency (UBA) in the version from May 14th, 2020 under section
2.1.3.1.
Technical Data
Power Supply: External USB Power Plug 5 V/ 1A
Battery: Bobbin Cell C ER26500, Lithium-Thionyl Chloride
Processor: ESP32-WROOM_32E (Xtensa Dual Core 32 Bit, 240 MHz, 520 KB RAM)
Wireless Connection:
WIFI ESP Built-in 2.4 GHz 802.11 b/g/n, bitrate in ‘n’ mode up to 150Mbps
Lora: SX1261, EU868 MHz, SF 7-12, TX16 dBm, RX: - 147 dBm @ 300 bps, Class A
Pressure Sensor Head:
Range : 0 … 1000 kPa (10 bar)
Overload: 150 Percent of maximum pressure
Connection: G ¼ “ female
Communication: I2C
Precision:
Built-in High-Precision Temperature Sensor
Dimensions (Main): 91 mm x 91 mm x 30 mm
Weight (Main Device): 105 gr
Weight (Sensor Head): 140 gr
Protection: Main Device: IP 65, Sensor Head: IP 67
User Interface: 4 colored LED, single touchless button
Environmental Conditions:
Shipment and Storage: -65 °C … 125 °C
Operation: - 20 °C … 50 °C
Rel. Humidity: 0...90 %
Users and Installation Manual: LoRaWAN Pressure Monitor (PRELWE02)
Copyright © 2022 Aqua-Scope Technologies, Sakala tn 7-2, 10141 Tallinn, Estonia, www.aqua-scope.com
Support and Contact
Should you encounter any problem, please give us the opportunity to address it before returning this
product. Please check our website www.aqua-scope.com and particularly the support section for answers
and help. You can also send a message to [email protected].
While the information in this manual has been compiled with great care, it may not be deemed an
assurance of product characteristics. Aqua-Scope shall be liable only to the degree specified in the terms
of sale and delivery. The reproduction and distribution of the documentation and software supplied with
this product and the use of its contents is subject to written authorization from Aqua-Scope. We reserve
the right to make any alterations that arise as the result of technical development.
Phone: +372 (0) 6248002
Web: www.aqua-scope.com
Declaration of Conformity
Aqua-Scope Technology OÜ, Sakala 7-2, 10141 Tallinn, Republic of Estonia, declares that
this radio emitting device works on the following frequences:
Български С настоящото Aqua-Scope Technology OÜ декларира, че този тип
радиосъоръжение PRELWE02 е в съответств ие с Директива 2014/53/ЕС. Цялостният текст на ЕС
декларацията за съответствие може да се намери н а следния интернет адрес: www.aqua-scope.com/ce.
Čeština Tímto Aqua-Scope Technology OÜ prohlašuje, že typ rádiového zařízení PRELWE02 je v souladu se
směrnicí 2014/53/EU. Úplné znění EU prohlášení o shodě je k dispozici na této internetové adrese: www.aqua-
scope.com/ce.
Dansk Hermed erklærer Aqua-Scope Technology OÜ, at radioudstyrstypen PRELWE02 er i overensstemmelse
med direktiv 2014/53/EU. EUoverensstemmelseserklæringens fulde tekst kan findes p følgende internetadresse:
www.aqua-scope.com/ce.
Deutsch Hiermit erklärt Aqua-Scope Technology OÜ, dass der Funkanlagentyp PRELWE02 der Richtlinie
2014/53/EU entspricht. Der vollständige Text der EU-Konformitätserklärung ist unter der folgenden
Internetadresse verfügbar: www.aqua-scope.com/ce.
Eesti Käesolevaga deklareerib Aqua-Scope Technology OÜ, et kesolev raadioseadme tp PRELWE02 vastab
direktiivi 2014/53/EL nuetele. ELi vastavusdeklaratsiooni tielik tekst on kttesaadav jrgmisel internetiaadressil:
www.aqua-scope.com/ce
English Hereby, Aqua-Scope Technology OÜ declares that the radio equipment type PRELWE02 is in compliance
with Directive 2014/53/EU. The full text of the EU declaration of conformity is available at the following internet
address: www.aqua-scope.com/ce
Español Por la presente, Aqua-Scope Technology OÜ declara que el tipo de equipo radioeléctrico PRELWE02 es
conforme con la Directiva 2014/53/UE. El texto completo de la declaracin UE de conformidad está disponible en la
direccin Internet siguiente: www.aqua-scope.com/ce
Users and Installation Manual: LoRaWAN Pressure Monitor (PRELWE02)
Copyright © 2022 Aqua-Scope Technologies, Sakala tn 7-2, 10141 Tallinn, Estonia, www.aqua-scope.com
Ελληνικά Με την παρούσα ο/η Aqua-Scope Technology OÜ, δηλώνει ότι ο ραδιοεξοπλισμός PRELWE02 πληροί
την οδηγία 2014/53/ΕΕ. Το πλήρες κείμενο της δήλωσης συμμόρ φωσης ΕΕ διατίθεται στην ακόλουθη ιστοσελίδα
στο διαδίκτυο: www.aqua-scope.com/ce
Français Le soussigné, Aqua-Scope Technology OÜ, déclare que l'équipement radioélectrique du type PRELWE02
est conforme la directive 2014/53/UE. Le texte complet de la déclaration UE de conformité est disponible
l'adresse internet suivante: www.aqua-scope.com/ce
Hrvatski Aqua-Scope Technology OÜ ovime izjavljuje da je radijska oprema tipa PRELWE02 u skladu s Direktivom
2014/53/EU. Cjeloviti tekst EU izjave o sukladnosti dostupan je na sljedećoj internetskoj adresi: www.aqua-
scope.com/ce
Italiano Il fabbricante, Aqua-Scope Technology OÜ, dichiara che il tipo di apparecchiatura radio PRELWE02
conforme alla direttiva 2014/53/UE. Il testo completo della dichiarazione di conformit UE disponibile al seguente
indirizzo Internet: www.aqua-scope.com/ce
Latviešu Ar šo Aqua-Scope Technology OÜ deklarē, ka radioiekārta PRELWE02 atbilst Direktīvai 2014/53/ES. Pilns
ES atbilstības deklarācijas teksts ir pieejams šādā interneta v ietnē: www.aqua-scope.com/ce Lietuvių Aš, Aqua-
Scope Technology OÜ, patvirtinu, kad radijo įrenginių tipas PRELWE02 atitinka Direktyvą 2014/53/ES. Visas ES
atitikties deklaracijos tekstas prieinamas šiuo internet adresu: www.aqua-scope.com/ce
Magyar Aqua-Scope Technology OÜ igazolja, hogy a PRELWE02 típus rádiberendezés megfelel a 2014/53/EU
irányelvnek. Az EUmegfelelőségi nyilatkozat teljes szövege elérhető a következő internetes címen: www.aqua-
scope.com/ce
Malti B'dan, Aqua-Scope Technology OÜ, niddikjara li dan it-tip ta' tagħmir tar-radju PRELWE02 huwa konformi
madDirettiva 2014/53/UE. It-test kollu tad-dikjarazzjoni ta' konformit tal-UE huwa disponibbli f'dan l-indirizz
talInternet li ġej: www.aqua-scope.com/ce
Nederlands Hierbij verklaar ik, Aqua-Scope Technology OÜ, dat het type radioapparatuur PRELWE02 conform is
met Richtlijn 2014/53/EU. De volledige tekst van de EUconformiteitsverklaring kan worden geraadpleegd op het
volgende internetadres: www.aqua-scope.com/ce
Polski Aqua-Scope Technology OÜ niniejszym oświadcza, że typ urządzenia radiowego PRELWE02 jest zgodny z
dyrektywą 2014/53/UE. Pełny tekst deklaracji zgodnośc I UE jest dostępny pod następującym adre sem
internetowym: www.aqua-scope.com/ce
Português O(a) abaixo assinado(a) Aqua-Scope Technology OÜ declara que o presente tipo de equipamento de
rádio PRELWE02 está em conformidade com a Diretiva 2014/53/UE. O texto integral da declarao de conformidade
está disponível no seguinte endereo de Internet: www.aqua-scope.com/ce
Română Prin prezenta Aqua-Scope Technology OÜ declară că tipul de echipamente PRELWE02 este în
conformitate cu Directiva 2014/53/UE. Textul integral al declarației UE de conformitate este disponibil la
următoarea adresă internet: www.aqua-scope.com/ce
Slovensko Aqua-Scope Technology OÜ potrjuje, da je tip radijske opreme PRELWE02 skladen z irektivo
2014/53/EU. Celotno besedilo izjave EU o skladnosti je na voljo na naslednjem spletnem naslovu: www.aqua-
scope.com/ce
Slovensky Aqua-Scope Technology OÜ týmto vyhlasuje, že rádiové zariadenie typu PRELWE02 je v slade so
smernicou 2014/53/EÚ. Úplné EÚ vyhlásenie o zhode je k dispozícii na tejto internetovej adrese: www.aqua-
Users and Installation Manual: LoRaWAN Pressure Monitor (PRELWE02)
Copyright © 2022 Aqua-Scope Technologies, Sakala tn 7-2, 10141 Tallinn, Estonia, www.aqua-scope.com
scope.com/ce
Soumi Aqua-Scope Technology OÜ vakuuttaa, että radiolaitetyyppi PRELWE02 on direktiivin 2014/53/EU
mukainen. EUvaatimustenmukaisuusvakuutuksen täysimittainen teksti on saatavilla seuraavassa
internetosoitteessa: www.aqua-scope.com/ce
Svenska Härmed försäkrar Aqua-Scope Technology OÜ att denna typ av radioutrustning PRELWE02
verensstmmer med direktiv 2014/53/EU. Den fullständiga texten till EUförsäkran om verensstämmelse finns på
följande webbadress: www.aqua-scope.com/ce
Disposal Guidelines
Do not dispose of electrical appliances as unsorted municipal waste, use separate collection
facilities. Contact your local government for information regarding the collection systems available.
If electrical appliances are disposed of in landfills or dumps, hazardous substances can leak into
the groundwater and get into the food chain, damaging health and well-being.
Users and Installation Manual: LoRaWAN Pressure Monitor (PRELWE02)