Pepperl+Fuchs LTC57 Manual de utilizare

Tip
Manual de utilizare

Acest manual este potrivit și pentru

SI00502O-D/98/A3/15.13
71239671
Betriebsanleitung
Instruction manual
Notice d'instructions
Pulscon
LTC50, LTC51, LTC57
2-wire, 4 mA ... 20 mA, HART
ATEX: II 1/2G Ex ia IIC T6-T1 Ga/Gb
II 1/2D Ex ia IIIC Txx°C Da/Db
SI00502O-D
DE – Sicherheitshinweise für elektrische Betriebsmittel für
explosionsgefährdete Bereiche, siehe Seite 5
EN – Safety instructions for electrical apparatus for explosion-
hazardous areas, see page 11
FR – Conseils de sécurité pour matériels électriques destinés aux
zones explosibles, regardez à la page 17
Pulscon LTC50, LTC51, LTC57
SI00502O-D
DOCT-3670 2015-03 266864
2
t pie mums tulkojumu J su valsts valod .
Istruzioni di sicurezza per apparecchiature elettriche certificate per
l'utilizzo in aree con pericolo di esplosione. Se il presente manuale non
risulta comprensibile potete ordinarcene una copia tradotta nella
vostra lingua.
it -
Con questa dichiarazione e con l'applicazione del marchio CE, il costruttore
Pepperl+Fuchs, assicura che il prodotto è conforme alle direttive europee
vigenti. Prova della conformità è fornita dall'osservanza delle direttive, delle
norme e dei documenti elencati.
Dichiarazione di conformità CE
Veiligheidsinstructies voor elektrisch materieel in explosiegevaarlijke
omgeving. Wanneer u deze handleiding niet kunt lezen, kunt u een in
uw landstaal vertaalde handleiding bij ons bestellen.
nl -
De leverancier Pepperl+Fuchs waarborgt met deze verklaring en het
aanbrengen van het CE-teken, dat dit product overeenstemt met de
geldende Europese richtlijnen. De geldende richtlijnen, normen en
documenten zijn aangegeven in de conformiteitsverklaring.
EG Conformiteitsverklaring
Turvallisuusohjeita sähkölaitteille, jotka on vahvistettu käytettäväksi
räjähdysvaarallisilla alueilla. Jos et ymmärrä tätä käsikirjaa, voit tilata
meiltä käännöksen omalla kansallisella kielelläsi.
fi -
Valmistaja Pepperl+Fuchs vakuuttaa tällä vaatimustenmukaisuustodistuksella
ja CE-merkin kiinnittämisellä, että tämä tuote täyttää sovellettavien
EU-direktiivien määräykset. Sovellettavat direktiivit, normit ja dokumentit on
merkitty vaatimustenmukaisuustodistukseen.
EU-vaatimustenmukaisuustodistus
Wskazówki dot. bezpieczeństwa dla urządzeń elektrycznych stosowanych
w obszarze zagrożonym wybuchem. Jeśli niniejsza instrukcja napisana
jest w języku, którym się nie posługujesz, możesz zamówić u nas
przetłumaczony dokument.
pl -
Producent Pepperl+Fuchs w niniejszej deklaracji zgodności wraz z
nadaniem znaku CE oświadcza, że produkt ten jest zgodny z obowiązującą
Europejską Dyrektywą. Zastosowane wytyczne, normy oraz dukumenty
podane są w deklaracji zgodnoś
Deklaracja zgodności WE
ci.
Säkerhetsföreskrifter för elektrisk utrustning certifierad för användning i
explosionsfarliga områden. Om du inte förstår denna manual, kan en
översatt kopia på ditt eget språk beställas från oss.
sv -
Pepperl+Fuchs försäkrar med vidstående försäkran om överensstämmelse
och med CE-märkningen att denna produkt överensstämmer med de
tillämpbara europeiska riktlinjerna. De tillämpade riktlinjerna, normerna
och dokumenten anges i försäkran om överensstämmelse.
EG-försäkran om överensstämmelse
Bezpečnostné pokyny pre elektrické zariadenie prevádzkované v
s nebezpečenstvom výbuchu. Ak nemáte možnost’ prečítat’ si
tento si u nás objednat’ návod preložený do svojho jazyka.
priestoroch
návod, môžete
sk -
Spoločnosť Pepperl+Fuchs vyhlasuje prostredníctvom tohto vyhlásenia
o konformite a použitím značky CE, že tento výrobok
Vyhlásenie o konformite s ES
vyhovuje príslušným
európskym smerniciam. Zmieňované smernice, normy a dokumenty sú
uvedené vo Vyhlásení o konformite.
Sikkerhedsforskrifter for elektriske apparater certificeret til brug i
eksplosionsfarlige områder. Hvis du ikke forstår denne manual,
kan en oversat kopi af den på dit eget sprog bestilles fra os.
da -
Med denne overensstemmelseserklæring og tilføjelsen af CE-mærket sikrer
producenten Pepperl+Fuchs, at produktet er i overensstemmelse med
relevante europæiske direktiver. Dokumentation for overensstemmelsen
gives i de anførte direktiver, standarder og dokumenter.
EF-overensstemmelseserklæring
Varnostni napotki glede električne opreme, namenjene za uporabo v
eksplozivnih območjih. Če teh navodil ne morete razumeti, lahko pri nas
naročite prevod v vaš jezik.
sl -
Pojasnilo glede potrdila o skladnosti EU
Proizvajalec Pepperl+Fuchs s to izjavo o skladnosti in navedbo oznake
CE izjavlja, da je ta izdelek skladen s predpisanimi evropskimi smernicami.
Upoštevane smernice, standardi in dokumenti so navedeni v izjavi o skladnosti.
Instruções de segurança para dispositivos eléctricos certificados para
utilização em áreas de risco de incêndio. Se não compreender este
manual, pode encomendar-nos directamente uma cópia na sua língua.
pt -
Com esta declaração de conformidade e a aplicação da marca CE, o
fabricante Pepperl+Fuchs, garante que o produto obedece às directivas
europeias a aplicar. As directivas, normas e documentos são apresentadas
na declaração de conformidade.
Declaração de conformidade CE
Bezpečnostní pokyny pro elektrické přístroje v místech s nebezpečím
výbuchu. Pokud nemáte možnost přečíst si tento návod, můžete si u nás
objednat návod přeložený do svého jazyka.
cs -
Společnost Pepperl+Fuchs prohlašuje prostřednictvím tohoto prohlášení
a použitím značky CE, že tento výrobek vyhovuje příslušným evropským
směrnicím Zmíněné směrnice jsou uvedeny v
Prohlášení o shodě.
Prohlášení o shodě s ES
. , normy a dokumenty
Biztonsági információk robbanásveszélyes területre való elektromos
eszközökhöz. Amennyiben nem tudja elolvasni ezt az útmutatót, akkor
megrendelheti az Ön anyanyelvére lefordítva is.
hu -
Az Pepperl+Fuchs mint gyártó jelen megfelelőségi nyilatkozattal és a
CE-jelzés felhelyezésével kijelenti, hogy ez a termék megfelel az alkalmazandó
sékoynávbazs.kenkevleynáriiapórue
dokumentumok a megfelelőségi nyilatkozatban fel vannak tüntetve.
EK-megfelelőségi nyilatkozat
Az alkalmazott irányelvek,
Instrucciones de seguridad de aparatos eléctricos homologados para su
utilización en áreas expuestas a riesgos de deflagración. Si no entiende
este manual, puede pedir un ejemplar en su idioma.
es -
Por la presente declaración y la inclusión de la marca CE, el fabricante
Pepperl+Fuchs, declara que el producto cumple con las directivas
europeas pertinentes. Las directivas, normas y documentos de aplicación
se indican en la declaración de conformidad.
Declaración de conformidad CE
Ohutusjuhised plahvatusohtlikus keskkonnas kasutatavate
elektriseadmete kohta. Kui Te ei saa käesolevast juhendist aru, võite
meilt tellida Teie riigikeelde tõlgitud juhendi.
et -
EL vastavusdeklaratsioon
Tootja Pepperl+Fuchs kinnitab juurdelisatud vastavusdeklaratsiooni
esitamisega ja CE-märgise kandmisega tootele, et käesolev toode vastab
kohaldatavate Euroopa Liidu direktiivide nõuetele.
Kohaldatavad direktiivid, standardid ja dokumendid on ära toodud
vastavusdeklaratsioonis.
el -
∆ήλωση πιστότητας ΕΚ
Με αυτή τη δήλωση πιστότητας και την τοποθέτηση του σήματος
ο κατασκευαστής δηλώνει, ότι αυτό το προϊόν
συμορφώνεται με τις ευρωπαϊκές οδηγίες που πρέπει να εφαρμοστούν.
Οι οδηγίες, τα πορότυπα και τα έγγραφα που εφαρμόστηκαν
αναφέρονται στη δήλωση πιστότητας.
CE Pepperl+Fuchs
Οδηγίες ασφαλείας ηλεκτρικών συσκευών για επικίνδυνες για έκρηξη
περιοχές.
αντίτυπο μεταφρασμένο
στη γλώσσα σας.
Σε περίπτωση που δεν μπορείτε να διαβάσετε αυτές τις
οδηγίες, τότε μπορείτε να παραγγείλετε ένα
lt -
Elektros įrenginio saugumo nurodymai, susiję su sprogimo zonomis.
Jeigu negalite perskaityti šios instrukcijos, kreipkitėsįmus, kad
užsisakytumėte įjūsųgimtąją kalbą išverstą instrukciją.
Gamintojas Pepperl+Fuchs šia atitikties deklaracija ir CE ženklinimu
patvirtina, kad gaminys atitinka taikytinas ES direktyvas. Taikomos
direktyvos, normos ir dokumentai yra pateikiami atitikties deklaracijoje.
EB atitikties deklaracija
lv -
Dro bas nor d jumi elektrisko darba instrumentu lieto anai apgabalos,
kas pak au spr dzienb stam bai. Ja Jums nav iesp ju izlas t os
nor d jumus, J s varat pas t
šīāīš
Ražotājs Pepperl+Fuchs ar šo atbilsbas apliecinājumu un CE zīmola
lietojumu apsprina, ka produkts izgatavots sakaņā ar atbilstošajām
Eiropas vadlīnijām. iemērotās vadlīnijas, normas un dokumenatrunā
atbilsbas apliecinājumā.
ES atbilsbas apliecinājums
P
Indicaţii de siguranţă pentru mijloacele de producţie electrice pentru zonele
periclitate de explozie. Dacă nu puteţi citi aceste instrucţiuni, atunci puteţi
comanda la noi instrucţiunile traduse în limba ţării dumneavoastră.
ro -
Producătorul Pepperl+Fuchs declară prin declaraţia de conformitate alăturată
şi prin aplicarea semnului CE că acest produs corespunde directivelor europene
aplicabile. Directivele, normele aplicate şi documentele sunt menţionate în
declaraţia de conformitate.
Declaraţie de conformitate CE
Правила за техниката на безопасност за електрически средства за
производство във взривоопасни зони. Ако не разбирате езика на
това ръководство има възможност да си поръчате при нас едно
ръководство, преведено на езика на Вашата страна.
bg -
.
Заявление за съответствие с EG
Производителят Pepperl+Fuchs декларира с това заявление за
съответствиеиспредявяванетонасертификата CE, че този продукт
отговаря на изискванията на съответните европейски директиви.
Прилаганите директиви, норми и документи са указани в заявлението
за съответствие
Pulscon LTC50, LTC51, LTC57
SI00502O-D
DOCT-3670 2015-03 266864
3
EU-Konformitätserklärung/EU-Declaration of conformity/
Déclaration UE de conformité
Pulscon LTC50, LTC51, LTC57
SI00502O-D
DOCT-3670 2015-03 266864
4
Pulscon LTC50, LTC51, LTC57
SI00502O-D
DOCT-3670 2015-03 266864
11
EN
Pulscon
LTC50, LTC51, LTC57
2-wire, 4 mA ... 20 mA, HART
Table of Contents
Associated documentation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Supplementary documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Manufacturer's certificates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Extended order code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Safety instructions: General . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Safety instructions: Special conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Safety instructions: Installation . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Safety instructions: Zone 0. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Temperature tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Connection data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Pulscon LTC50, LTC51, LTC57
SI00502O-D
DOCT-3670 2015-03 266864
12
EN
Associated
documentation
This document is an integral part of the following Operating Instructions:
BA01000O, BA01001O, BA01004O
The Operating Instructions pertaining to the device apply.
Supplementary
documentation
Explosion-protection manual
Manufacturer's
certificates
EU-Declaration of conformity
seepage3
EC type-examination certificate
Certificate number:
DEKRA 14 ATEX 0117X
Extended order code The extended order code is indicated on the nameplate, which is affixed to the device in such a way
that it is clearly visible. Additional information about the nameplate is provided in the associated
Operating Instructions.
Structure of the extended order code
Basic specifications
The features that are absolutely essential for the device (mandatory features) are specified in the
basic specifications. The number of positions depends on the number of features available.
The selected option of a feature can consist of several positions.
Optional specifications
The optional specifications describe additional features for the device (optional features). The
number of positions depends on the number of features available.
More detailed information about the device is provided in the following tables. These tables describe
the individual positions and IDs in the extended order code which are relevant to hazardous
locations.
Device type Basic specifications Optional specifications
LTC5X X-XXXXX-XXXXX-XX XXXXX + XXXXXXXXXX
X = Placeholder
At this position, an option (number or letter) selected from the specification is displayed
instead of the placeholders.
Pulscon LTC50, LTC51, LTC57
SI00502O-D
DOCT-3670 2015-03 266864
13
EN
Device type: LTC50, LTC51, LTC57
Basic specifications
Optional specifications
Safety instructions:
General
Staff must meet the following conditions for mounting, electrical installation, commissioning and
maintenance of the device:
Be suitably qualified for their role and the tasks they perform
Be trained in explosion protection
Be familiar with national regulations (e. g. IEC/EN 60079-14)
Install the device according to the manufacturer's instructions and national regulations.
Do not operate the device outside the specified electrical, thermal and mechanical parameters.
Only use the device in media to which the wetted materials have sufficient durability.
Refer to the temperature tables for the relationship between the permitted ambient temperature
for the sensor and/or transmitter, depending on the range of application, and the temperature
class.
Modifications to the device can affect the explosion protection and must be carried out by staff
authorized to perform such work by Pepperl+Fuchs.
When replacing the probe electronics or opening the connection between the remote cable and
the probe, a jumper plug must be used or a short-circuit must be established between the probe
contact and the potential equalization conductor to avoid electrostatically charging the probe.
After mounting and connecting the probe, ingress protection of the housing must be at least IP65
in accordance with EN 60529.
Perform the following to achieve the degree of protection:
Screw the cover tight.
Mount the cable entry correctly.
When using in hybrid mixtures (gas and dust occurring simultaneously), observe additional
measures for explosion protection.
Safety instructions:
Special conditions
Permitted ambient temperature range at the electronics housing: -40 °C T
amb +80 °C.
Observe the information in the temperature tables.
Selected Option Position Description
Approval LTC5X-X-XXXXX-XXXXX-XX XXXXX SX ATEX II 1/2G Ex ia IIC T6-T1 Ga/Gb
ATEX II 1/2D Ex ia IIIC Txx°C Da/Db
Electrical output LTC5X-X-XXXXX-XXXXX-XX XXXXX IH
ID
IE
2-wire, 4 mA ... 20 mA, HART
2-wire, 4 mA ... 20 mA, HART, switch output (PFS)
2-wire, 4 mA ... 20 mA, HART, 4 mA ... 20 mA
Display, operation LTC5X-X-XXXXX-XXXXX-XX XXXXX B
D
E
without display, via communication
SD02, 4-line, push-buttons and data backup function
SD03, 4-line, illuminated, touch control and data backup function
Housing LTC5X-X-XXXXX-XXXXX-XX XXXXX A2 GT20 dual compartment, alu coated
LTC51-X-XXXXX-XXXXX-XX XXXXX
LTC57-X-XXXXX-XXXXX-XX XXXXX
A3 GT18 dual compartment, 316L
Seal LTC50-X-XXXXX-XXXXX-XX XXXXX 2 Viton, -20 °C ... 80 °C
LTC51-X-XXXXX-XXXXX-XX XXXXX 3
4
5
EPDM, -40 °C ... 120 °C
Kalrez, -20 °C ... 200 °C
Viton, -30 °C ... 150 °C
LTC57-X-XXXXX-XXXXX-XX XXXXX 3
5
EPDM, -40 °C ... 120 °C
Viton, -30 °C ... 150 °C
Selected Option Position Description
Probe design XXXXXXXXXX B Sensor remote, 3 m cable, detachable, with mounting bracket
Pulscon LTC50, LTC51, LTC57
SI00502O-D
DOCT-3670 2015-03 266864
14
EN
Safety instructions:
Installation
Figure 1
AZone1, Zone21
1 Tank; Zone 0, Zone 1, or Zone 20, Zone 21
2 Electronic insert
3 Certified associated apparatus
4 Potential equalization line
5 Potential equalization
After aligning (rotating) the housing, retighten the fixing screw (see Operating Instructions).
When mounting the device:
Exclude any mechanical damage or friction during the application.
Pay particular attention to flow conditions and tank fittings.
Continuous service temperature of the connecting cable: -40 °C ... +85 °C; in accordance with
the range of service temperature taking into account additional influences of the process
conditions (Tamb,min), (Tamb, max +20 K).
Only use certified cable entries or sealing plugs.
The metal sealing plugs supplied meet this requirement.
Before operation:
Screw in the cover all the way.
Tighten the securing clamp on the cover.
Intrinsic safety
The device is only suitable for connection to certified, intrinsically safe equipment with explosion
protection Ex ia/Ex ib.
The intrinsically safe input power circuit of the device is isolated from ground. If the device is only
equipped with one input, the dielectric strength of the input is at least 500 Vrms. If the device is
equipped with more than one input, the dielectric strength of each individual input to ground is at
least 500 Vrms, and the dielectric strength of the inputs vis-à-vis one another is also at least
500 Vrms.
Observe the pertinent guidelines when interconnecting intrinsically safe circuits
(e. g. IEC/EN 60079-14, Proof of Intrinsic Safety).
The device can be connected to the Pepperl+Fuchs service interface: refer to the Operating
Instructions and specifications in the "Overvoltage protection" chapter.
Basic specification, Option "Electrical output" = IH
When the device is connected to certified intrinsically safe circuits of Category Ex ib for
Equipment Groups IIC and IIB, the type of protection changes to Ex ib IIC T6 and Ex ib IIB T6.
Do not operate the probe in Zone 0 if connecting to an intrinsically safe circuit of Category Ex ib.
Basic specification, Option "Electrical output" = ID, IE
When the intrinsically safe Ex ia circuits of the device are connected to certified intrinsically safe
circuits of Category Ex ib for Equipment Groups IIC or IIB, the type of protection changes to
Ex ib[ia] IIC or Ex ib[ia] IIB.
Regardless of the power supply, all the internal circuits correspond to Ex ia IIC type of protection
(e. g. service interface, external display, sensor).
Potential equalization
Integrate the device into the local potential equalization.
A
+
1
2
4
4
5
3
Pulscon LTC50, LTC51, LTC57
SI00502O-D
DOCT-3670 2015-03 266864
15
EN
Overvoltage protection
If an overvoltage protection according to IEC/EN 60079-14 against atmospheric over voltages is
required: no other circuits may leave the housing during normal operation without additional
measures.
For installations which require overvoltage protection to comply with national regulations or
standards (e. g. IEC/EN 60079-14), install the device using overvoltage protection.
Observe the safety instructions of the overvoltage protection.
Safety instructions:
Zone 0
In the event of potentially explosive vapor/air mixtures, only operate the device under
atmospheric conditions.
Temperature: -20 °C ... +60 °C
Pressure: 80 kPa ... 110 kPa (0.8 bar ... 1.1 bar)
Air with normal oxygen content, usually 21 % (V/V)
If no potentially explosive mixtures are present, or if additional protective measures have
been taken according to EN 1127-1, the device may also be operated under non-atmospheric
conditions in accordance with the manufacturer's specifications.
Associated devices with galvanic isolation between the intrinsically safe and non-intrinsically
safe circuits are preferred.
If there is a risk of dangerous potential differences within Zone 0 (e. g. through the occurrence of
atmospheric electricity), implement suitable measures for intrinsically safe circuits in Zone 0
(e. g. in accordance with the requirements of IEC/EN 60079-14).
Temperature tables seepage23
Connection data Basic specification, option "Approval" = SX
Ex ia
Power supply and signal circuit with protection type: intrinsic safety Ex ia IIC or IIIC.
Basic specification, Option "Electrical output" = IH (TRC [21])
Terminal 1 (+), 2 (–)
Power supply Ex ia IIC: Power supply Ex ia IIIC:
Ui = 30 V
Ii = 300 mA
Pi= 1 W
Ui = 30 V
Ii = 250 mA
Pi= 0.6 W (Tamb T8C)
effective inner inductance Li = 0 µH
effective inner capacitance Ci = 12 nF
effective inner inductance Li = 0 µH
effective inner capacitance Ci = 12 nF
Basic specification, Option "Electrical output" = ID (TRC [02])
Terminal 1 (+), 2 (–) Terminal 3 (+), 4 (–)
Power supply: Switch output (PFS):
Ui = 30 V
Ii = 300 mA
Pi= 1 W
Ui = 30 V
Ii = 300 mA
Pi= 1 W
effective inner inductance Li = 0 µH
effective inner capacitance Ci = 5 nF
effective inner inductance Li = 0 µH
effective inner capacitance Ci = 3 nF
effective inner capacitance to ground Ci = 5.28 nF
Basic specification, Option "Electrical output" = IE (TRC [04])
Terminal 1 (+), 2 (–) Terminal 3 (+), 4 (–)
Power supply: Output 4 mA ...20 mA:
Ui = 30 V
Ii = 300 mA
Pi= 1 W
Ui = 30 V
Ii = 300 mA
Pi= 1 W
effective inner inductance Li = 0 µH
effective inner capacitance Ci = 30 nF
effective inner inductance Li = 0 µH
effective inner capacitance Ci = 30 nF
Pulscon LTC50, LTC51, LTC57
SI00502O-D
DOCT-3670 2015-03 266864
16
EN
Service interface (CDI)
Taking the following values into consideration, the device can be connected to the certified service
tool or a similar interface:
Service interface
Ui = 7.3 V
effective inner inductance Li = negligible
effective inner capacitance Ci = negligible
Uo = 7.3 V
Io = 100 mA
Po= 160 mW
Lo(mH) =
Co (µF) =
5.00
0.73
2.00
1.20
1.00
1.60
0.50
2.00
0.20
2.60
0.10
3.20
0.05
4.00
0.02
5.50
0.01
7.30
0.005
10.00
0.002
12.70
0.001
12.70
Pulscon LTC50, LTC51, LTC57
SI00502O-D
DOCT-3670 2015-03 266864
23
Temperaturtabellen/Temperature tables/
Tableaux des températures
Inhaltsverzeichnis/Table of Contents/Sommaire
Allgemeine Hinweise/General notes/Généralités. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Diagramm/Diagram/Diagramme . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Sonden-Design: kompakt/Probe design: compact/Construction de sonde: compacte
Sonde und Elektronikgehäuse/Probe and electronics housing/Sonde et boîtier de
l'électronique: Zone 1
LTC50 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
LTC51 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
LTC57 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Sonde/Probe/Sonde: Zone 0
Elektronikgehäuse/Electronics housing/Boîtier de l'électronique: Zone 1
LTC5X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Sonde und Elektronikgehäuse/Probe and electronics housing/
Sonde et boîtier de l'électronique: Zone 20, Zone 21
LTC5X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Sonden-Design: abgesetzt/Probe design: remote/Construction de sonde: séparée
Sonde/Probe/Sonde: Zone 0, Zone 1
Elektronikgehäuse/Electronics housing/Boîtier de l'électronique: Zone 1
LTC5X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Pulscon LTC50, LTC51, LTC57
SI00502O-D
DOCT-3670 2015-03 266864
24
Allgemeine Hinweise Wenn nicht anders angegeben, beziehen sich die Positionen immer auf die Grundspezifikation.
Hinweis!
Zulässigen Temperaturbereich an der Sonde beachten.
Auswahltabelle
General notes Unless otherwise indicated, the positions always refer to the basic specification.
Note!
Observe the permitted temperature range at the probe.
Selection table
Généralités Sauf indication contraire, les positions se réfèrent toujours aux spécifications de base.
Note!
Tenir compte de la gamme de température admissible à la sonde.
Tableau de sélection
Zulassung Gehäuse
SX ATEX II 1/2G Ex ia IIC T6-T1 Ga/Gb
ATEX II 1/2D Ex ia IIIC Txx°C Da/Db
A2
A3
GT20 Zweikammer, Alu beschichtet
GT18 Zweikammer, 316L
Elektrischer Ausgang Transmission-Code des
Anschlussklemmenmoduls
Kanäle
IH
ID
IE
2-Draht, 4 mA ... 20 mA, HART
2-Draht, 4 mA ... 20 mA, HART,
Schaltausgang (PFS)
2-Draht, 4 mA ... 20 mA, HART,
4 mA ... 20 mA
TRC [21]; TRC [01] 1
TRC [02]
TRC [04]
1 oder 2 Kanäle benutzt
1 oder 2 Kanäle benutzt
1siehe Typenschild
Approval Housing
SX ATEX II 1/2G Ex ia IIC T6-T1 Ga/Gb
ATEX II 1/2D Ex ia IIIC Txx°C Da/Db
A2
A3
GT20 dual compartment, Alu coated
GT18 dual compartment, 316L
Elektrical output Transmission code of the
terminal module
Channels
IH
ID
IE
2-wire, 4 mA ... 20 mA, HART
2-wire, 4 mA ... 20 mA, HART, switch
output (PFS)
2-wire, 4 mA ... 20 mA, HART,
4 mA ... 20 mA
TRC [21]; TRC [01] 1
TRC [02]
TRC [04]
1 or 2 channels used
1 or 2 channels used
1see nameplate
Agrément Boîtier
SX ATEX II 1/2G Ex ia IIC T6-T1 Ga/Gb
ATEX II 1/2D Ex ia IIIC Txx°C Da/Db
A2
A3
GT20 double compartiment, alu revêtu
GT18 double compartiment, 316L
Sortie électrique Code de transmission du
module de raccordement
Voies
IH
ID
IE
2-fils, 4 mA ... 20 mA, HART
2-fils, 4 mA ... 20 mA, HART, sortie tout
ou rien (PFS)
2-fils, 4 mA ... 20 mA, HART,
4 mA ... 20 mA
TRC [21]; TRC [01] 1
TRC [02]
TRC [04]
1 ou 2 voies utilisées
1 ou 2 voies utilisées
1voir plaque signalétique
Pulscon LTC50, LTC51, LTC57
SI00502O-D
DOCT-3670 2015-03 266864
25
Diagramm/Diagram/
Diagramme
Beispieldiagramme zu den Temperaturtabellen/Example diagrams to the temperature tables/
Diagrammes d'exemple aux tableaux des températures
Abbildung/Figure/Figure 1
A Version 1
B Version 2
Tamb Umgebungstemperatur/Ambient temperature/Température ambiante
TpProzesstemperatur/Process temperature/Température de process
A
T
amb
B
Tp
Tp
P 1
P 1
P 2
P 2
P 5
P 5
P 6
P 3
P 3
P 4
P 4
T
amb
Pulscon LTC50, LTC51, LTC57
SI00502O-D
DOCT-3670 2015-03 266864
26
Sonden-Design: kompakt/Probe design: compact/Construction de sonde : compacte
Sonde und Elektronikgehäuse/Probe and electronics housing/Sonde et boîtier de
l'électronique : Zone 1
LTC50
Elektrischer Ausgang/Electrical output/Sortie électrique = IH (TRC [21])
Gehäuse/Housing/Boîtier = A2
Elektrischer
Ausgang/
Electrical output/
Sortie électrique
Temperaturklasse/
Temperature class/
Classe de
température
P 1 P 2 P 3 P 4 P 5 P 6
TpTamb TpTamb TpTamb TpTamb TpTamb TpTamb
IH T6 (85 °C) -20 °C 60 °C 60 °C 60 °C 80 °C 56 °C 80 °C -20 °C -20 °C -20 °C
Elektrischer Ausgang/Electrical output/Sortie électrique = ID (TRC [02])
Gehäuse/Housing/Boîtier = A2
Elektrischer
Ausgang/
Electrical output/
Sortie électrique
Temperaturklasse/
Temperature class/
Classe de
température
P 1 P 2 P 3 P 4 P 5 P 6
TpTamb TpTamb TpTamb TpTamb TpTamb TpTamb
ID
1 Kanal benutzt/
1 channel used/
1 voie utilisée
T6 (85 °C) -20 °C 60 °C 60 °C 60 °C 80 °C 56 °C 80 °C -20 °C -20 °C -20 °C
ID
2 Kanäle benutzt/
2 channels used/
2 voies utilisées
T6 (85 °C) -20 °C 51 °C 51 °C 51 °C 80 °C 49 °C 80 °C -20 °C -20 °C -20 °C
Elektrischer Ausgang/Electrical output/Sortie électrique = IE (TRC [04])
Gehäuse/Housing/Boîtier = A2
Elektrischer
Ausgang/
Electrical output/
Sortie électrique
Temperaturklasse/
Temperature class/
Classe de
température
P 1 P 2 P 3 P 4 P 5 P 6
TpTamb TpTamb TpTamb TpTamb TpTamb TpTamb
IE
1 Kanal benutzt/
1 channel used/
1 voie utilisée
T6 (85 °C) -20 °C 60 °C 60 °C 60 °C 80 °C 56 °C 80 °C -20 °C -20 °C -20 °C
IE
2 Kanäle benutzt/
2 channels used/
2 voies utilisées
T6 (85 °C) -20 °C 54 °C 54 °C 54 °C 80 °C 52 °C 80 °C -20 °C -20 °C -20 °C
Pulscon LTC50, LTC51, LTC57
SI00502O-D
DOCT-3670 2015-03 266864
27
Sonde und Elektronikgehäuse/Probe and electronics housing/Sonde et boîtier de
l'électronique : Zone 1
LTC51
Elektrischer Ausgang/Electrical output/Sortie électrique = IH (TRC [21])
Gehäuse/Housing/Boîtier = A3
Elektrischer
Ausgang/
Electrical output/
Sortie électrique
Temperaturklasse/
Temperature class/
Classe de
température
P 1 P 2 P 3 P 4 P 5 P 6
TpTamb TpTamb TpTamb TpTamb TpTamb TpTamb
IH T6 (85 °C) -40 °C 60 °C 60 °C 60 °C 85 °C 52 °C 85 °C -40 °C -40 °C -40 °C
T5 (100 °C) -40 °C 75 °C 75 °C 75 °C 100 °C 67 °C 100 °C -40 °C -40 °C -40 °C
T4 (135 °C) -40 °C 80 °C 81 °C 80 °C 135 °C 68 °C 135 °C -40 °C -40 °C -40 °C
T3 (200 °C) -40 °C 80 °C 81 °C 80 °C 200 °C 49 °C 200 °C -40 °C -40 °C -40 °C
Gehäuse/Housing/Boîtier = A2
Elektrischer
Ausgang/
Electrical output/
Sortie électrique
Temperaturklasse/
Temperature class/
Classe de
température
P 1 P 2 P 3 P 4 P 5 P 6
TpTamb TpTamb TpTamb TpTamb TpTamb TpTamb
IH T6 (85 °C) -40 °C 60 °C 60 °C 60 °C 85 °C 54 °C 85 °C -40 °C -40 °C -40 °C
T5 (100 °C) -40 °C 75 °C 75 °C 75 °C 100 °C 69 °C 100 °C -40 °C -40 °C -40 °C
T4 (135 °C) -40 °C 80 °C 81 °C 80 °C 135 °C 70 °C 135 °C -40 °C -40 °C -40 °C
T3 (200 °C) -40 °C 80 °C 81 °C 80 °C 200 °C 57 °C 200 °C -40 °C -40 °C -40 °C
Elektrischer Ausgang/Electrical output/Sortie électrique = ID (TRC [02])
Gehäuse/Housing/Boîtier = A3
Elektrischer
Ausgang/
Electrical output/
Sortie électrique
Temperaturklasse/
Temperature class/
Classe de
température
P 1 P 2 P 3 P 4 P 5 P 6
TpTamb TpTamb TpTamb TpTamb TpTamb TpTamb
ID
1 Kanal benutzt/
1 channel used/
1 voie utilisée
T6 (85 °C) -40 °C 60 °C 60 °C 60 °C 85 °C 52 °C 85 °C -40 °C -40 °C -40 °C
T5 (100 °C) -40 °C 75 °C 75 °C 75 °C 100 °C 67 °C 100 °C -40 °C -40 °C -40 °C
T4 (135 °C) -40 °C 80 °C 80 °C 80 °C 135 °C 67 °C 135 °C -40 °C -40 °C -40 °C
T3 (200 °C) -40 °C 80 °C 80 °C 80 °C 200 °C 49 °C 200 °C -40 °C -40 °C -40 °C
ID
2 Kanäle benutzt/
2 channels used/
2 voies utilisées
T6 (85 °C) -40 °C 51 °C 51 °C 51 °C 85 °C 43 °C 85 °C -40 °C -40 °C -40 °C
T5 (100 °C) -40 °C 66 °C 66 °C 66 °C 100 °C 58 °C 100 °C -40 °C -40 °C -40 °C
T4 (135 °C) -40 °C 75 °C 75 °C 75 °C 135 °C 60 °C 135 °C -40 °C -40 °C -40 °C
T3 (200 °C) -40 °C 75 °C 75 °C 75 °C 200 °C 45 °C 200 °C -40 °C -40 °C -40 °C
Gehäuse/Housing/Boîtier = A2
Elektrischer
Ausgang/
Electrical output/
Sortie électrique
Temperaturklasse/
Temperature class/
Classe de
température
P 1 P 2 P 3 P 4 P 5 P 6
TpTamb TpTamb TpTamb TpTamb TpTamb TpTamb
ID
1 Kanal benutzt/
1 channel used/
1 voie utilisée
T6 (85 °C) -40 °C 60 °C 60 °C 60 °C 85 °C 54 °C 85 °C -40 °C -40 °C -40 °C
T5 (100 °C) -40 °C 75 °C 75 °C 75 °C 100 °C 69 °C 100 °C -40 °C -40 °C -40 °C
T4 (135 °C) -40 °C 80 °C 80 °C 80 °C 135 °C 69 °C 135 °C -40 °C -40 °C -40 °C
T3 (200 °C) -40 °C 80 °C 80 °C 80 °C 200 °C 56 °C 200 °C -40 °C -40 °C -40 °C
ID
2 Kanäle benutzt/
2 channels used/
2 voies utilisées
T6 (85 °C) -40 °C 51 °C 51 °C 51 °C 85 °C 44 °C 85 °C -40 °C -40 °C -40 °C
T5 (100 °C) -40 °C 66 °C 66 °C 66 °C 100 °C 59 °C 100 °C -40 °C -40 °C -40 °C
T4 (135 °C) -40 °C 75 °C 75 °C 75 °C 135 °C 63 °C 135 °C -40 °C -40 °C -40 °C
T3 (200 °C) -40 °C 75 °C 75 °C 75 °C 200 °C 50 °C 200 °C -40 °C -40 °C -40 °C
Pulscon LTC50, LTC51, LTC57
SI00502O-D
DOCT-3670 2015-03 266864
28
Elektrischer Ausgang/Electrical output/Sortie électrique = IE (TRC [04])
Gehäuse/Housing/Boîtier = A3
Elektrischer
Ausgang/
Electrical output/
Sortie électrique
Temperaturklasse/
Temperature class/
Classe de
température
P 1 P 2 P 3 P 4 P 5 P 6
TpTamb TpTamb TpTamb TpTamb TpTamb TpTamb
IE
1 Kanal benutzt/
1 channel used/
1 voie utilisée
T6 (85 °C) -40 °C 60 °C 60 °C 60 °C 85 °C 51 °C 85 °C -40 °C -40 °C -40 °C
T5 (100 °C) -40 °C 75 °C 75 °C 75 °C 100 °C 66 °C 100 °C -40 °C -40 °C -40 °C
T4 (135 °C) -40 °C 80 °C 80 °C 80 °C 135 °C 68 °C 135 °C -40 °C -40 °C -40 °C
T3 (200 °C) -40 °C 80 °C 80 °C 80 °C 200 °C 48 °C 200 °C -40 °C -40 °C -40 °C
IE
2 Kanäle benutzt/
2 channels used/
2 voies utilisées
T6 (85 °C) -40 °C 54 °C 54 °C 54 °C 85 °C 46 °C 85 °C -40 °C -40 °C -40 °C
T5 (100 °C) -40 °C 69 °C 69 °C 69 °C 100 °C 61 °C 100 °C -40 °C -40 °C -40 °C
T4 (135 °C) -40 °C 78 °C 78 °C 78 °C 135 °C 64 °C 135 °C -40 °C -40 °C -40 °C
T3 (200 °C) -40 °C 78 °C 78 °C 78 °C 200 °C 48 °C 200 °C -40 °C -40 °C -40 °C
Gehäuse/Housing/Boîtier = A2
Elektrischer
Ausgang/
Electrical output/
Sortie électrique
Temperaturklasse/
Temperature class/
Classe de
température
P 1 P 2 P 3 P 4 P 5 P 6
TpTamb TpTamb TpTamb TpTamb TpTamb TpTamb
IE
1 Kanal benutzt/
1 channel used/
1 voie utilisée
T6 (85 °C) -40 °C 60 °C 60 °C 60 °C 85 °C 53 °C 85 °C -40 °C -40 °C -40 °C
T5 (100 °C) -40 °C 75 °C 75 °C 75 °C 100 °C 68 °C 100 °C -40 °C -40 °C -40 °C
T4 (135 °C) -40 °C 80 °C 80 °C 80 °C 135 °C 70 °C 135 °C -40 °C -40 °C -40 °C
T3 (200 °C) -40 °C 80 °C 80 °C 80 °C 200 °C 56 °C 200 °C -40 °C -40 °C -40 °C
IE
2 Kanäle benutzt/
2 channels used/
2 voies utilisées
T6 (85 °C) -40 °C 54 °C 54 °C 54 °C 85 °C 48 °C 85 °C -40 °C -40 °C -40 °C
T5 (100 °C) -40 °C 69 °C 69 °C 69 °C 100 °C 63 °C 100 °C -40 °C -40 °C -40 °C
T4 (135 °C) -40 °C 78 °C 78 °C 78 °C 135 °C 66 °C 135 °C -40 °C -40 °C -40 °C
T3 (200 °C) -40 °C 78 °C 78 °C 78 °C 200 °C 53 °C 200 °C -40 °C -40 °C -40 °C
Pulscon LTC50, LTC51, LTC57
SI00502O-D
DOCT-3670 2015-03 266864
29
Sonde und Elektronikgehäuse/Probe and electronics housing/Sonde et boîtier de
l'électronique : Zone 1
LTC57
Elektrischer Ausgang/Electrical output/Sortie électrique = IH (TRC [21])
Gehäuse/Housing/Boîtier = A3
Elektrischer
Ausgang/
Electrical output/
Sortie électrique
Temperaturklasse/
Temperature class/
Classe de
température
P 1 P 2 P 3 P 4 P 5 P 6
TpTamb TpTamb TpTamb TpTamb TpTamb TpTamb
IH T6 (85 °C) -40 °C 60 °C 60 °C 60 °C 85 °C 54 °C 85 °C -40 °C -40 °C -40 °C
T5 (100 °C) -40 °C 75 °C 75 °C 75 °C 100 °C 69 °C 100 °C -40 °C -40 °C -40 °C
T4 (135 °C) -40 °C 80 °C 81 °C 80 °C 135 °C 70 °C 135 °C -40 °C -40 °C -40 °C
T3 (200 °C) -40 °C 80 °C 81 °C 80 °C 185 °C 60 °C 185 °C -40 °C -40 °C -40 °C
Gehäuse/Housing/Boîtier = A2
Elektrischer
Ausgang/
Electrical output/
Sortie électrique
Temperaturklasse/
Temperature class/
Classe de
température
P 1P 2P 3P 4P 5P 6
TpTamb TpTamb TpTamb TpTamb TpTamb TpTamb
IH T6 (85 °C) -40 °C 60 °C 60 °C 60 °C 85 °C 55 °C 85 °C -40 °C -40 °C -40 °C
T5 (100 °C) -40 °C 75 °C 75 °C 75 °C 100 °C 70 °C 100 °C -40 °C -40 °C -40 °C
T4 (135 °C) -40 °C 80 °C 81 °C 80 °C 135 °C 72 °C 135 °C -40 °C -40 °C -40 °C
T3 (200 °C) -40 °C 80 °C 81 °C 80 °C 185 °C 64 °C 185 °C -40 °C -40 °C -40 °C
Elektrischer Ausgang/Electrical output/Sortie électrique = ID (TRC [02])
Gehäuse/Housing/Boîtier = A3
Elektrischer
Ausgang/
Electrical output/
Sortie électrique
Temperaturklasse/
Temperature class/
Classe de
température
P 1 P 2 P 3 P 4 P 5 P 6
TpTamb TpTamb TpTamb TpTamb TpTamb TpTamb
ID
1 Kanal benutzt/
1 channel used/
1 voie utilisée
T6 (85 °C) -40 °C 60 °C 60 °C 60 °C 85 °C 54 °C 85 °C -40 °C -40 °C -40 °C
T5 (100 °C) -40 °C 75 °C 75 °C 75 °C 100 °C 69 °C 100 °C -40 °C -40 °C -40 °C
T4 (135 °C) -40 °C 80 °C 80 °C 80 °C 135 °C 69 °C 135 °C -40 °C -40 °C -40 °C
T3 (200 °C) -40 °C 80 °C 80 °C 80 °C 185 °C 59 °C 185 °C -40 °C -40 °C -40 °C
ID
2 Kanäle benutzt/
2 channels used/
2 voies utilisées
T6 (85 °C) -40 °C 51 °C 51 °C 51 °C 85 °C 45 °C 85 °C -40 °C -40 °C -40 °C
T5 (100 °C) -40 °C 66 °C 66 °C 66 °C 100 °C 60 °C 100 °C -40 °C -40 °C -40 °C
T4 (135 °C) -40 °C 75 °C 75 °C 75 °C 135 °C 63 °C 135 °C -40 °C -40 °C -40 °C
T3 (200 °C) -40 °C 75 °C 75 °C 75 °C 185 °C 53 °C 185 °C -40 °C -40 °C -40 °C
Gehäuse/Housing/Boîtier = A2
Elektrischer
Ausgang/
Electrical output/
Sortie électrique
Temperaturklasse/
Temperature class/
Classe de
température
P 1 P 2 P 3 P 4 P 5 P 6
TpTamb TpTamb TpTamb TpTamb TpTamb TpTamb
ID
1 Kanal benutzt/
1 channel used/
1 voie utilisée
T6 (85 °C) -40 °C 60 °C 60 °C 60 °C 85 °C 55 °C 85 °C -40 °C -40 °C -40 °C
T5 (100 °C) -40 °C 75 °C 75 °C 75 °C 100 °C 70 °C 100 °C -40 °C -40 °C -40 °C
T4 (135 °C) -40 °C 80 °C 80 °C 80 °C 135 °C 71 °C 135 °C -40 °C -40 °C -40 °C
T3 (200 °C) -40 °C 80 °C 80 °C 80 °C 185 °C 63 °C 185 °C -40 °C -40 °C -40 °C
ID
2 Kanäle benutzt/
2 channels used/
2 voies utilisées
T6 (85 °C) -40 °C 51 °C 51 °C 51 °C 85 °C 46 °C 85 °C -40 °C -40 °C -40 °C
T5 (100 °C) -40 °C 66 °C 66 °C 66 °C 100 °C 61 °C 100 °C -40 °C -40 °C -40 °C
T4 (135 °C) -40 °C 75 °C 75 °C 75 °C 135 °C 65 °C 135 °C -40 °C -40 °C -40 °C
T3 (200 °C) -40 °C 75 °C 75 °C 75 °C 185 °C 57 °C 185 °C -40 °C -40 °C -40 °C
Pulscon LTC50, LTC51, LTC57
SI00502O-D
DOCT-3670 2015-03 266864
30
Elektrischer Ausgang/Electrical output/Sortie électrique = IE (TRC [04])
Gehäuse/Housing/Boîtier = A3
Elektrischer
Ausgang/
Electrical output/
Sortie électrique
Temperaturklasse/
Temperature class/
Classe de
température
P 1 P 2 P 3 P 4 P 5 P 6
TpTamb TpTamb TpTamb TpTamb TpTamb TpTamb
IE
1 Kanal benutzt/
1 channel used/
1 voie utilisée
T6 (85 °C) -40 °C 60 °C 60 °C 60 °C 85 °C 53 °C 85 °C -40 °C -40 °C -40 °C
T5 (100 °C) -40 °C 75 °C 75 °C 75 °C 100 °C 68 °C 100 °C -40 °C -40 °C -40 °C
T4 (135 °C) -40 °C 80 °C 80 °C 80 °C 135 °C 71 °C 135 °C -40 °C -40 °C -40 °C
T3 (200 °C) -40 °C 80 °C 80 °C 80 °C 185 °C 60 °C 185 °C -40 °C -40 °C -40 °C
IE
2 Kanäle benutzt/
2 channels used/
2 voies utilisées
T6 (85 °C) -40 °C 54 °C 54 °C 54 °C 85 °C 48 °C 85 °C -40 °C -40 °C -40 °C
T5 (100 °C) -40 °C 69 °C 69 °C 69 °C 100 °C 63 °C 100 °C -40 °C -40 °C -40 °C
T4 (135 °C) -40 °C 78 °C 78 °C 78 °C 135 °C 66 °C 135 °C -40 °C -40 °C -40 °C
T3 (200 °C) -40 °C 78 °C 78 °C 78 °C 185 °C 57 °C 185 °C -40 °C -40 °C -40 °C
Gehäuse/Housing/Boîtier = A2
Elektrischer
Ausgang/
Electrical output/
Sortie électrique
Temperaturklasse/
Temperature class/
Classe de
température
P 1 P 2 P 3 P 4 P 5 P 6
TpTamb TpTamb TpTamb TpTamb TpTamb TpTamb
IE
1 Kanal benutzt/
1 channel used/
1 voie utilisée
T6 (85 °C) -40 °C 60 °C 60 °C 60 °C 85 °C 55 °C 85 °C -40 °C -40 °C -40 °C
T5 (100 °C) -40 °C 75 °C 75 °C 75 °C 100 °C 70 °C 100 °C -40 °C -40 °C -40 °C
T4 (135 °C) -40 °C 80 °C 80 °C 80 °C 135 °C 72 °C 135 °C -40 °C -40 °C -40 °C
T3 (200 °C) -40 °C 80 °C 80 °C 80 °C 185 °C 65 °C 185 °C -40 °C -40 °C -40 °C
IE
2 Kanäle benutzt/
2 channels used/
2 voies utilisées
T6 (85 °C) -40 °C 54 °C 54 °C 54 °C 85 °C 49 °C 85 °C -40 °C -40 °C -40 °C
T5 (100 °C) -40 °C 69 °C 69 °C 69 °C 100 °C 64 °C 100 °C -40 °C -40 °C -40 °C
T4 (135 °C) -40 °C 78 °C 78 °C 78 °C 135 °C 68 °C 135 °C -40 °C -40 °C -40 °C
T3 (200 °C) -40 °C 78 °C 78 °C 78 °C 185 °C 61 °C 185 °C -40 °C -40 °C -40 °C
Pulscon LTC50, LTC51, LTC57
SI00502O-D
DOCT-3670 2015-03 266864
31
Sonde/Probe/Sonde : Zone 0
Elektronikgehäuse/Electronics housing/Boîtier de l'électronique : Zone 1
1LTC50, ohne abgesetzten Sensor/without remote sensor/sans sonde séparée = -20 °C
LTC5X
Elektrischer Ausgang/Electrical output/Sortie électrique = IH (TRC [21])
Gehäuse/Housing/Boîtier = A2, A3
Elektrischer
Ausgang/
Electrical output/
Sortie électrique
Temperaturklasse/
Temperature class/
Classe de
température
P 1 P 2 P 3 P 4 P 5 P 6
TpTamb TpTamb TpTamb TpTamb2TpTamb2TpTamb
IH T6 (85 °C) -20 °C 60 °C 60 °C 60 °C 60 °C 60 °C 60 °C -40 °C -20 °C -40 °C
Elektrischer Ausgang/Electrical output/Sortie électrique = ID (TRC [02])
Gehäuse/Housing/Boîtier = A2, A3
Elektrischer
Ausgang/
Electrical output/
Sortie électrique
Temperaturklasse/
Temperature class/
Classe de
température
P 1 P 2 P 3 P 4 P 5 P 6
TpTamb TpTamb TpTamb TpTamb2TpTamb2TpTamb
ID
1 Kanal benutzt/
1 channel used/
1 voie utilisée
T6 (85 °C) -20 °C 60 °C 60 °C 60 °C 60 °C 60 °C 60 °C -40 °C -20 °C -40 °C
ID
2 Kanäle benutzt/
2 channels used/
2 voies utilisées
T6 (85 °C) -20 °C 51 °C 51 °C 51 °C 60 °C 49 °C 60 °C -40 °C -20 °C -40 °C
Elektrischer Ausgang/Electrical output/Sortie électrique = IE (TRC [04])
Gehäuse/Housing/Boîtier = A2, A3
Elektrischer
Ausgang/
Electrical output/
Sortie électrique
Temperaturklasse/
Temperature class/
Classe de
température
P 1 P 2 P 3 P 4 P 5 P 6
TpTamb TpTamb TpTamb TpTamb1TpTamb1TpTamb
IE
1 Kanal benutzt/
1 channel used/
1 voie utilisée
T6 (85 °C) -20 °C 60 °C 60 °C 60 °C 60 °C 60 °C 60 °C -40 °C -20 °C -40 °C
IE
2 Kanäle benutzt/
2 channels used/
2 voies utilisées
T6 (85 °C) -20 °C 53 °C 53 °C 53 °C 60 °C 53 °C 60 °C -40 °C -20 °C -40 °C
Pulscon LTC50, LTC51, LTC57
SI00502O-D
DOCT-3670 2015-03 266864
32
Sonde und Elektronikgehäuse/Probe and electronics housing/Sonde et boîtier de
l'électronique : Zone 20, Zone 21
Gehäuse/Housing/Boîtier = A2, A3
LTC5X
Elektrischer Ausgang/Electrical output/Sortie électrique = IH (TRC [21])
T = Tamb + 5 K
Elektrischer Ausgang/Electrical output/Sortie électrique= ID (TRC [02])
1 Kanal benutzt/1 channel used/1 voie utilisée 2 Kanäle benutzt/2 channeles used/2 voies
utilisées
T = Tamb + 5 K T = Tamb + 10 K
Elektrischer Ausgang/Electrical output/Sortie électrique = IE (TRC [04])
1 Kanal benutzt/1 channel used/1 voie utilisée 2 Kanäle benutzt/2 channeles used/2 voies
utilisées
T = Tamb + 5 K T = Tamb + 10 K
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24

Pepperl+Fuchs LTC57 Manual de utilizare

Tip
Manual de utilizare
Acest manual este potrivit și pentru