Tesla TT34TP21-1232IAW Manual de utilizare

Categorie
Aparate de aer condiționat cu sistem divizat
Tip
Manual de utilizare
SPLIT-TYPE
AIR CONDITIONER
USER
MANUAL
For R32 DC Inverter models:
TT34TP21W-1232IAWT
TT34TP21W-1232IAWBIG
TT51TP21W-1832IAWT
TT34TP21W-1232IA
TT51TP21-1832IA
TT51TP21-1832IAW
TT68TP21-2432IAW
TT27TP81-0932IAWT
TT34TP81-1232IAWT
TT51TP81-1832IAWT
TT68TP81-2432IAWT
TT34TP91-1232IAWT
TT34TP91-1232IAWUVT
TT51TP91-1832IAWT
TT34TP21-1232IAW
TT34TP21-1232IAWUV
TT51TP21-1832IAWUV
TT68TP21-2432IAWUV
TT27TP21-0932IAWT
TT34TP21-1232IAWT
TT51TP21-1832IAWT
TT27TP21W-0932IAWT
Ver. 2023
HU MKD
BIH/
MNE RO SLO SRBENG BG GR HR
OPERATING INSTRUCTION
Note: All the pictures in this manual are just schematic diagrams, the actual is the standard. Please read
this owner’s manual carefully and thoroughly before operating the unit! Take care of this manual for future
reference. ***T-marked models have a built-in tray heater that turns on automatically when the outside
temperature is below 3°C
UPUTE ZA UPOTREBU
Napomena: Sve slike u ovom priručniku su samo shematski dijagrami, fizički proizvod je standard. Molimo
Vas da pažljivo i temeljito pročitate ovo uputstvo za upotrebu prije korištenja uređaja! Čuvajte ovaj priručnik
za buduće korištenje. ***Modeli s oznakom T imaju ugrađeni grijač posude koji se automatski uključuje
kada je vanjska temperatura ispod 3°C
FELHASZNÁLÓI KÉZIKÖNYV
Megjegyzés: A kézikönyvben található képek csak sematikus ábrák, az aktuális a szabvány. Kérjük, figyelmesen
olvassa el ezt a kézikönyvet mielőtt működtetné az eszközt! Őrizze meg ezt a kézikönyvet a későbbiekre is.
***A T jelzéssel ellátott modellek beépített tálcafűtéssel rendelkeznek, amely automatikusan bekapcsol, ha a
külső hőmérséklet 3°C alá csökken.
ΕΓΧΕΙΡΙΔΙΟ ΧΡΉΣΉΣ
Σημείωση: Οι εικόνες στο παρόν εγχειρίδιο είναι σχεδιαγράμματα, ανατρέξτε στο πραγματικό προϊόν. Διαβάστε
προσεκτικά τις προφυλάξεις στο παρόν εγχειρίδιο προτού θέσετε τη μονάδα σε λειτουργία! Φυλάξτε το παρόν
εγχειρίδιο για μελλοντική χρήση. ***Τα μοντέλα με το σημείο σήμανσης T διαθέτουν ενσωματωμένο δίσκο
θέρμανσης που ενεργοποιείται αυτόματα, όταν η εξωτερική θερμοκρασία είναι κάτω από 3°C
ИНСТРУКЦИЯ ЗА УПОТРЕБА
Забележка: Всички снимки в тази инструкция са само схематични диаграми, действителните са
стандартните. Моля, прочетете внимателно тази инструкция за употреба преди да започнете работа с
уреда! Запазете тази инструкция за бъдещи справки. ***Моделите с Т-маркировка имат вграден нагревател
на тавата за отцеждане , който се включва автоматично, когато външната температура е под 3°C
PRIROČNIK ZA UPORABO
Opomba: Vse slike v tem priročniku so le shematske risbe, dejansko stanje je standard. Prosimo, da pred
uporabo skrbno in temeljito preberete ta priročnik za uporabo! Priročnik shranite za kasnejšo uporabo.
***Modeli z oznako T imajo vgrajen grelec pladnja zunaje enote, ki se samodejno vklopi, ko zunanja
temperatura pade pod 3°C
MANUAL DE UTILIZARE
Nota: Fotografiile din acest manual sunt doar diagrame schematice. Vă rugăm să citiți “Manualul de Utilizare”
cu atenție, înainte de a utiliza aerul condiționat, pentru a asigura funcționarea corespunzătoare. Păstrați
manualul pentru referințe ulterioare. ***Modelele marcate T au un încălzitor încorporta în tavă care pornește
automat când temperatura exterioară este sub 3°C
ENG
HR
HU
GR
BG
UPUTSTVO ZA UPOTREBU
Napomena: Sve slike u ovom priručniku su samo šematski dijagrami, fizički proizvod je standard. Molimo Vas
da pažljivo i temeljno pročitate ovo uputstvo za upotrebu prije korišćenja uređaja! Sačuvajte ovo uputstvo za
buduću upotrebu. *** Modeli sa oznakom T imaju ugrađen grijač tacne koji se automatski uključuje kada je
vanjska temperatura ispod 30°C
BIH/
MNE
SLO
RO
УПАТСТВО ЗА УПОТРЕБА
Напомена: Сите слики во овој прирачник се само шематски дијаграми, физичкиот производ е
стандард. Ве молиме внимателно и теменлно да го причитате ова упатство за употреба пред
користење на уредот! Сочувајте го ова упатство за идна употреба. ***Моделите кои на крајот се со
ознака Т имаат вграден грејач кој автоматски се вклучува кога надворешната температура е под 3°C
MKD
UPUTSTVO ZA UPOTREBU
Napomena: Sve slike u ovom priručniku su samo šematski dijagrami, fizički proizvod je standard. Molimo
Vas da pažljivo i temeljno pročitate ovo uputstvo za upotrebu pre korišćenja uređaja! Sačuvajte ovo
uputstvo za buduću upotrebu. ***Modeli sa oznakom T imaju ugrađeni grejač tacne koji se automatski
uključuje kada je spoljna temperatura ispod 3°C
SRB
3
ENG
Read this guide before installing and using the appliance.
During the installation of the indoor and outdoor units the access to the working area should be forbidden to
children. Unforeseeable accidents could happen.
Make sure that the base of the outdoor unit is firmly fixed.
Check that air cannot enter the refrigerant system and check for refrigerant leaks when moving the air
conditioner.
Carry out a test cycle after installing the air conditioner and record the operating data.
Protect the indoor unit with a fuse of suitable capacity for the maximum input current or with another overload
protection device.
Ensure that the mains voltage corresponds to that stamped on the rating plate. Keep the switch or power plug
clean. Insert the power plug correctly and firmly into the socket, thereby avoiding the risk of electric shock or
fire due to insufficient contact.
Check that the socket is suitable for the plug , otherwise have the socket changed.
The appliance must be fitted with means for disconnection from the supply mains having a contact separation
in all poles that provide full disconnection under overvoltage category III conditions, and these means must be
incorporated in the fixed wiring in accordance with the wiring rules.
The air conditioner must be installed by professional or qualified persons.
Do not install the appliance at a distance of less than 50 cm from inflammable substances (alcohol, etc.) or from
pressurised containers (e.g. spray cans).
If the appliance is used in areas without the possibility of ventilation, precautions must be taken to prevent any
leaks of refrigerant gas from remaining in the environment and creating a danger of fire
The packaging materials are recyclable and should be disposed of in the separate waste bins .Take the air
conditioner at the end of its useful life to a special waste collection centre for disposal.
Only use the air conditioner as instructed in this booklet. These instructions are not intended to cover every
possible condition and situation . As with any electrical household appliance , common sense and caution are
therefore always recommended for installation, operation and maintenance.
The appliance must be installed in accordance with applicable national regulations.
Before accessing the terminals , all the power circuits must be disconnected from the power supply.
The appliance shall be installed in accordance with national wiring regulations.
This appliance can be used by children aaged from 8 years and above and persons with reduced physical,
sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or
instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall
not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
Do not try to install the conditioner alone; always contact specialized technical personnel.
Cleaning and maintenance must be carried out by specialized technical personnel. In any case disconnect the
appliance from the mains electricity supply before carrying out any cleaning or maintenance.
Ensure that the mains voltage corresponds to that stamped on the rating plate. Keep the switch or power plug
clean. Insert the power plug correctly and firmly into the socket , thereby avoiding the risk of electric shock or
fire due to insufficient contact.
Do not pull out the plug to switch off the appliance when it is in operation, since this could create a spark and
cause a fire, etc.
This appliance has been made for air conditioning domestic environments and must not be used for any other
purpose , such as for drying clothes, cooling food, etc.
Always use the appliance with the air filter mounted . The use of the conditioner without air filter could cause an
excessive accumulation of dust or waste on the inner parts of the device with possible subsequent failures.
The user is responsible for having the appliance installed by a qualified technician , who must check that it is
earthed in accordance with current legislation and insert a thermomagnetic circuit breaker.
The batteries in remote controller must be recycled or disposed of properly. Disposal of Scrap Batteries ---
Please discard the batteries as sorted municipal waste at the accessible collection point.
Never remain directly exposed to the flow of cold air for a long time. The direct and prolonged exposition
SAFETY RULES AND RECOMMENDATIONS
FOR THE INSTALLER
SAFETY PRECAUTIONS
4
ENG
to cold air could be dangerous for your health .Particular care should be taken in the rooms where there are
children , old or sick people.
If the appliance gives off smoke or there is a smell of burning, immediately cut off the pow er supply and contact
the Service Centre.
The prolonged use of the device in such conditions could cause fire or electrocution.
Have repairs carried out only by an authorised Service Centre of the manufacturer . Incorrect repair could
expose the user to the risk of electric shock, etc.
Unhook the automatic switch if you foresee not to use the device for a long time. The airflow direction must be
properly adjusted.
Only use the air conditioner as instructed in this booklet. These instructions are not intended to cover every
possible condition and situation. As with any electrical household appliance, common sense and caution are
therefore always recommended for installation , operation and maintenance.
Ensure that the appliance is disconnected from the power supply when it will remain inoperative for a long
period and before carrying out any cleaning or maintenance.
Selecting the most suitable temperature can prevent damage to the appliance.
Do not bend, tug or compress the power cord since this could damage it. Electrical shocks or fire are probably
due to a damaged power cord. Specialized technical personnel only must replace a damaged power cord.
Do not use extensions or gang modules.
Do not touch the appliance when barefoot or parts of the body are wet or damp.
Do not obstruct the air inlet or outlet of the indoor or the outdoor unit. The obstruction of these openings
causes a reduction in the operative efficiency of the conditioner with possible consequent failures or damages.
In no way alter the characteristics of the appliance.
Do not install the appliance in environments where the air could contain gas , oil or sulphur or near sources of
heat.
This appliance is not intended for use by persons (including children ) with reduced physical, sensory or mental
capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction
concerning use of the appliance by a person responsible for their safety.
Do not climb onto or place any heavy or hot objects on top of the appliance.
Do not leave windows or doors open for long when the air conditioner is operating.
Do not direct the airflow onto plants or animals.
A long direct exposition to the flow of cold air of the conditioner could have negative effects on plants and
animals.
Do not put the conditioner in contact with water. The electrical insulation could be damaged and thus causing
electrocution.
Do not climb onto or place any objects on the outdoor unit
Never insert a stick or similar object into the appliance. It could cause injury.
Children should be supervised to ensure that they do not play with the appliance. If the supply cord is damaged,
it must be replaced by the manufacturer,its service agent or similarly qualified persons in order to avoid a
hazard.
SAFETY RULES AND PROHIBITIONS
5
ENG
NAMES OF PARTS
Indoor unit
Outdoor unit
Note: This figure shown may be
different from the actual object.
Please take the latter as the
standard.
Mounting plate
Air filter
Air inlet
Front panel
Emergency button
Refrigerant
connecting pipe
Air inlet
Air outlet
Air outlet Air deflector and flap
Wiring cover
Drainage pipe
Connection wiring
Valve protective cover
Gas valve
(Low pressure valve)
Liquid valve
(High pressure valve)
With the protective
cover removed
6
ENG
Indoor Display
No. LED Function
1Indicator for Timer, temperature and Error codes.
2Lights up during Timer operation.
3SLEEP mode
The shape and position of switches and indicators may be different according to the model, but their function
is the same.
7
ENG
REMOTE CONTROLLER
Remote control DISPLAY
No. Button Function
1Battery indicator
2Auto Mode
3Cooling Mode
4Dry Mode
5Fan only Mode
6Heating Mode
7ECO Mode
8Timer
9Temperature indicator
10 Fan speed:
Auto/ low/ low-mid/ mid/ mid-high/ high
11 Mute function
12 TURBO function
13 Up-down auto swing
14 Left-right auto swing
15 SLEEP function
16 Health function
17 I FEEL function
18 8 C heating function
19 Signal indicator
20 Gentle wind
21 Child-Lock
22 Display ON/OFF
23 GEN function
24 Self-Clean function
25 Anti-mildew function
The display and some functions of the remote control may vary according to the model.
8
ENG
The display and some functions of the remote control may vary according to the model.
The shape and position of buttons and indicators may vary according to the model, but their function is the
same.
The unit confirms the correct reception of each button with the beep.
No. Button Function
1To turn on/off the air conditioner .
2To decrease temperature, or Timer setting hours.
3To increase temperature, or Timer setting hours.
4MODE To select the mode of operation (AUTO, COOL, DRY, FAN, HEAT).
5ECO To activate/deactivate the ECO function.
Long press to activate/deactivate the 8C heating function (depending on models).
6TURBO To activate/deactivate the TURBO function.
7FAN To select the fan speed of auto/mute/low/low-mid/mid/mid-high/high/turbo.
8TIMER To set the time for timer on/off.
9SLEEP To switch-on/off the function SLEEP.
10 DISPLAY To switch-on/off the LED display.
11 To stop or start horizontal louver movement or set the desired up/down air flow
direction.
12 To stop or start horizontal louver movement or set the desired left/rightair flow
direction.
13 I FEEL To switch-on/off the I FEEL function.
14 MUTE To switch-on/off the MUTE function.
Long press to activate/deactivate the GEN function (depending on models).
15 MODE +
TIMER To activate/deactivate the CHILD-LOCK function.
16 CLEAN To activate/deactivate the SELF-CLEAN function (depending on models).
17 FAN + MUTE To activate/deactivate the GENTLE WIND function (depending on models).
18 HEALTH To activate/deactivate the HEALTH function (depending on models).
19 ANTI-MILDEW To activate/deactivate the ANTI-MILDEW function.
9
ENG
Use 2 pieces LRO3 AAA (1.5V) batteries.
Do not use rechargeable batteries.
Replace the old batteries with new ones of the same type when the
display is no longer legible.
Do not dispose batteries as unsorted municipal waste.
Collection of such waste separately for special treatment is necessary.
Each time when insert the batteries in the remote controller for the first time, you can set the Cooling only or
Heating pump control type. As soon as you insert the batteries, turn off the remote controller, and operate as
below.
1. Long press the button, until the ( ) icon flash, to set the Cooling only type.
2. Long press the button, until the ( ) icon flash, to set the Heating pump type.
Note: If you set the remote control in cooling mode, it will not be possible to activate the heating function in
units with a heating pump. If you need to reset, take out the batteries and install again.
You can program the temperature display between C and F.
1. Press and hold the button over 5 seconds to get into the change mode;
2. Press and hold the button, until it switch to C and F;
3. Then release the pressing and wait for 5 seconds, the function will be selected.
Replacement of Batteries
Remove the battery cover plate from the rear of the remote control, by pressing and sliding it in direction as the
arrow. Install the batteries by putting ( -) at the side with spring on the remote controller. Reinstall the battery cover
by sliding it into place.
Note:
1. Direct the remote control toward the Air conditioner.
2. Check that there are no objects between the remote control and the Signal receptor in the indoor unit.
3. Never leave the remote control exposed to the rays of the sun.
4. Keep the remote control at a distance of at least 1m from the television or other electrical appliances.
The cooling function allows the air
conditioner to cool the room and
reduce Air humidity at the same time.
Fan mode, air ventilation only.
To activate the cooling function (COOL), press the
button until the symbol appears on the
display. With the button or set a temperature lower
than that of the room.
To set the FAN mode, press until appears
on the display.
Cooling mode
FAN MODE (Not FAN button)
This function reduces the humidity
of the air to make the room more
comfortable.
To set the DRY mode, Press until appears
in the display. An automatic function of pre-setting is
activated.
DRY MODE
Automatic mode.
To set the AUTO mode, press until
appears on the display. In AUTO mode the run mode
will be set automatically according to the room
temperature.
AUTO MODE
10
ENG
The heating function allows the air
conditioner to heat the room.
Change the operating fan speed.
To automatic switch on the appliance.
To automatic switch off the appliance.
To activate the heating function (HEAT), press the
button until the symbol appears on the
display. With the button or set a temperature higher
than that of the room.
Press button to set the running fan speed, it can
be set to AUTO/ MUTE/ LOW/ LOW-MID / MID/ MID-
HIGH/ HIGH/ TURBO speed circularly.
When the unit is switch-off, you can set the TIMER ON.
To set the time of automatic switch-on as below:
1. Press button first time to set the switch-on,
and will appear on the remote display and
flashes.
2. Press or to button to set desired Timer-on time.
Each time you press the button, the time increases/
When the unit is switch-on, you can set the TIMER OFF.
To set the time of automatic switch-off, as below:
1. Confirm the appliance is ON.
2. Press the button at first time to set the
switch-off.
Press or to set the needed timer.
3. Press button at the second time to confirm.
CANCEL it by press button.
Note: All programming should be operated within 5
seconds, otherwise the setting will be cancelled.
1. Press the button SWING to activate the louver,
1.1 Press to activate the horizontal flaps to swing
from up to down, the will appear on the remote
display.
1.2 Press to active the vertical deflectors to swing
from left to right, the will appear on the remote
display.
1.3 Do it again to stop the swing movement at the
current angle.
2. If the vertical deflectors are positioned manually
which placed under the flaps, they allow to move the
air flow direct to rightward or leftward.
3. Long press or over 3 seconds to select more
angles of the airflow direction.
1. Long press and button together
to active this function, and do it again to deactivate
this function.
2. Under this function, no single button will active.
HEATING MODE
FAN SPEED function (FAN
button)
TIMER function ---- TIMER ON
TIMER function ---- TIMER OFF
SWING function
Child-Lock function
In HEATING operation, the appliance can
automatically activate a defrost cycle, which is
essential to clean the frost on the condenser so
as to recover its heat exchange function. This
procedure usually lasts for 2-10 minutes. During
defrosting, indoor unit fan stop operation.
After defrosting, it resumes to HEATING mode
automatically.
(For North American market) If necessary, you
can press ECO button 10 times within 8 seconds
under heating mode to start the forced defrosting.
It will defrost the outdoor ice much more fast.
decreases by half an hour between 0 and 10 hours
and by one between 10 and 24 hours.
3. Press button second time to confirm.
4. After Timer-on setting, set the needed mode (Cool/
Heat/ Auto/ Fan/ Dry), by press the button.
And set the needed fan speed, by press
button. And press or to set the needed operation
temperature.
CANCEL it by press button.
11
ENG
Pre-setting automatic operating program.
In this mode the appliance automatically
sets the operation to save energy.
Switch ON/OFF the LED display on
panel.
Press button to activate the SLEEP function,
and appears on the display.
Press again to cancel this function.
After 10 hours running in sleep mode, the air
conditioner will change to the previous setting mode.
Press button to active the function, the will
appear on the remote display. Do it again to deactivate
this function.
This function enables the remote control to measure the
temperature at its current location, and send this signal
to the air conditioner to optimize the temperature
around you and ensure the comfort.
It will automatically deactivate 2 hours later.
Press the button, the appears on the display,
and the appliance will run in ECO mode.
Press again to cancel it.
Note: The ECO function is available in both COOLING
and HEATING modes.
Press button to switch off the LED
display on the panel. Press again to switch on the
LED display.
1. Turn on the indoor unit at first, and long press
button 3 seconds to active, and do it again to
deactivate this function.
2. Under this function, short press button to
select the General type L3 - L2 - L1 - OF.
3. Select OF and wait 2 seconds to exit it.
Only optional for some heating pump inverter
appliance.
To active this function, turn off the indoor unit at first,
then press button then you will hear a beep,
will appear on the indoor LED, and will
appear on the remote display .
1. This function helps carry away the accumulated dirt,
bacteria, etc from the indoor evaporator.
2. This function will run about 30 minutes, and it will
return to the pre-setting mode. You can press
button to cancel this function during the process.
You will hear 2 beeps when its finished or cancelled.
To activate turbo function, press the button,
and will appear on the display. Press again to
cancel this function. In COOL/ HEAT mode, when you
select TURBO feature, the appliance will turn to quick
COOL or quick HEAT mode, and operate the highest
fan speed to blow strong airflow.
1. Press button to active this function, and
will appears on the remote display. Do it again to
deactivate this function.
2. When the MUTE function runs, the remote controller
will display the auto fan speed, and the indoor unit
will operate at lowest fan speed to be quiet feeling.
3. When press FAN/ TURBO button, the MUTE function
will be cancel. MUTE function can not be activated
under dry mode.
SLEEP function
I FEEL function (Optional)
ECO function
DISPLAY function (Indoor
display)
GEN function (Optional)
SELF-CLEAN function
(Optional)
TURBO function
MUTE function
Never position Flaps manually, the delicate
mechanism might seriously damaged!
Its normal if there is some noise during this
function process, as plastic materials expand with
heat and contract with cold.
We suggest operating this function at the following
ambient conditions to avoid certain safety
protection features.
Never put fingers, sticks or other objects into the
air inlet or outlet vents. Such accidental contact
with live parts might cause unforeseeable damage
or injury.
Indoor unit Temp < 86°F (30°C)
Outdoor unit 41°F (5°C) < Temp < 86°F (30°C)
12
ENG
It’s suggested to utilize this function every 3
months.
Attempt to use the air conditioner under the temperature beyond the specified range may cause the air
conditioner protection device to start and the air conditioner may fail to operate. Therefore, try to use the air
conditioner in the following temperature conditions.
Characteristics of heating operation (applicable to Heating pump)
Preheating:
When the heating function is enabled, the indoor unit will take 2~5 minutes for preheating, after that the air
conditioner will start heating and blows warm air.
Defrosting:
During heating, when the outdoor unit frosted, the air conditioner will enable the automatic defrosting function
to improve the heating effect. During defrosting, the indoor and outdoor fans stop running. The air conditioner
will resume heating automatically after defrosting finish.
With the power supply connected, restart the air conditioner after shutdown, or switch it to other mode during
operation, and the air conditioner protection device will start. The compressor will resume operation after 3
minutes.
1. Long press button over 3 seconds to active
this function, and will appear on the
remote display. Do it again to deactivate this function.
2. This function will auto start the heating mode when
the room temperature is lower than 8C (46F), and it
will return to standby if the temperature reaches 9C
(48F).
3. If the room temperature is higher than 18C (64F),
the appliance will cancel this function automatically.
1. Turn on the indoor unit, and change to COOL mode,
then long press and button
together 3 seconds to active this function, will
appear on the display.
Do it again to deactivate it.
2. This function will auto close the vertical flaps, and give
you the comfortable gentle wind feeling.
1. Turn on the indoor unit at first, press to
active this function, will appear on the display.
Do it again to deactivate it.
2. When the HEALTH function is initiated, the Ionizer/
Plasma/ Bipolar Ionizer/ UVC Lights (depending on
models) will be energized and running.
1. In mode COOLING/ DRY, press
button to active this function, and will appear on
the remote display;
2. When turn off the air conditioner from the mode
COOLING/ DRY, the indoor unit will continue run
about 15 minutes to dry the indoor unit;
3. Press it again or select other modes to cancel this
function.
8�C heating function (Optional)
Gentle Wind function
(Optional)
Health function (Optional)
ANTI-MILDEW (Optional)
Temperature Mode
Heating Cooling Dry
Room temperature 0°C~30°C17°C~32°C
Outdoor temperature
-20°C~30°C
(Low temperature heating:
-25°C~30°C)
T1 climate: 15°C~53°C
(Low temperature cooling: -15°C~53°C)
T3 climate: 15°C~55°C
Inverter air conditioner:
OPERATION INSTRUCTIONS
13
ENG
Emergency button:
Open the panel and find the emergency button on the electronic control box when the remote controller fails .
(Always press the emergency button with insulation material.)
Current status Operation Respond Enter mode
Standby Press the emergency button once It beeps briefly once. Cooling mode
Standby (Only for
heating pump)
Press the emergency button twice
in 3 seconds It beeps briefly twice. Heating mode
Running Press the emergency button once It keeps beeping for a
while Off mode
control-box cover
(open the panel of indoor unit)
ON/OFF
INSTRUCTION FOR SERVICING (R32)
1. Check the information in this manual to find out the dimensions of space needed for proper installation of the
device, including the minimum distances allowed compared to adjacent structures.
2. Appliance shall be installed, operated and stored in a room with a floor area larger than 4m2.
3. The installation of pipe-work shall be kept to a minimum.
4. The pipe-work shall be protected from physical damage, and shall not be installed in an unventilated space if
the space is smaller than 4m2 .
5. The compliance with national gas regulations shall be observed.
6. The mechanical connections shall be accessible for maintenance purposes.
7. Follow the instructions given in this manual for handling, installing, cleaning, maintaining and disposing of the
refrigerant.
8. Make sure ventilation openings clear of obstruction.
9. Notice:The servicing shall be performed only as recommended by the manufacturer.
10. Warning: The appliance shall be stored in a well-ventilated area where the room size corresponds to the room
area as specified for operation.
11. Warning:The appliance shall be stored in a room without continuously operating open flames (for example
an operating gas appliance) and ignition sources (for example an operating electric heater).
12. The appliance shall be stored so as to prevent mechanical damage from occurring.
13. It is appropriate that anyone who is called upon to work on a refrigerant circuit should hold a valid and up-to-
date certificate from an assessment authority accredited by the industry and recognizing their competence
to handle refrigerants, in accordance with the assessment specification recognized in the industrial sector
concerned. Service operations should only be carried out in accordance with the recommendations of the
equipment manufacturer. Maintenance and repair operations that require the assistance of other qualified
persons must be conducted under the supervision of the person competent for the use of flammable
refrigerants.
14. Every working procedure that affects safety means shall only be carried out by competent persons.
14
ENG
Caution: Risk of fire Operating instructions Read technical manual
15. Warning:
Do not use means to accelerate the defrosting process or to clean, other than those recommended by the
manufacturer.
The appliance shall be stored in a room without continuously operating ignition sources (for example: open
flames, an operating gas appliance or an operating electric heater.
Do not pierce or burn.
Be aware that refrigerants may not contain an odour.
16. Information on servicing:
1. Checks to the area
Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure
that the risk of ignition is minimized. For repair to the refrigerating system, the following precautions shall be
complied with prior to conducting work on the system.
2. Work procedure
Work shall be undertaken under a controlled procedure so as to minimize the risk of a flammable gas or
vapour being present while the work is being performed.
3. General work area
All maintenance staff and others working in the local area shall be instructed on the nature of work being
carried out. Work in confined spaces shall be avoided. The area around the workspace shall be sectioned off.
Ensure that the conditions within the area have been made safe by control of flammable material.
4. Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the
technician is aware of potentially flammable atmospheres. Ensure that the leak detection equipment being
used is suitable for use with flammable refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe
5. Presence of fire extinguisher
If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire
extinguishing equipment shall be available to hand. Have a dry powder or CO2 fire extinguisher adjacent to
the charging area.
6. No ignition sources
No person carrying out work in relation to a refrigeration system which involves exposing any pipe work shall
use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition
sources, including cigarette smoking, should be kept sufficiently far away from the site of installation, repairing,
removing and disposal, during which refrigerant can possibly be released to the surrounding space. Prior to
work taking place, the area around the equipment is to be surveyed to make sure that there are no flammable
hazards or ignition risks. “No Smoking” signs shall be displayed.
7. Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or
conducting any hot work. A degree of ventilation shall continue during the period that the work is carried
out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into the
atmosphere.
8. Checks to the refrigeration equipment
Where electrical components are being changed, they shall be fit for the purpose and to the correct
specification. At all times the manufacturer’s maintenance and service guidelines shall be followed. If in doubt
consult the manufacturer’s technical department for assistance.
The following checks shall be applied to installations using flammable refrigerants:
- The charge size is in accordance with the room size within which the refrigerant containing parts are installed;
- The ventilation machinery and outlets are operating adequately and are not obstructed;
- If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of
refrigerant;
- Marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be
corrected;
- Refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any
substance which may corrode refrigerant containing components, unless the components are constructed of
materials which are inherently resistant to being corroded or are suitably protected against being so corroded.
9. Checks to electrical devices
15
ENG
Repair and maintenance to electrical components shall include initial safety checks and component inspection
procedures. If a fault exists that could compromise safety, then no electrical supply shall be connected to
the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to
continue operation, an adequate temporary solution shall be used. This shall be reported to the owner of the
equipment so all parties are advised.
Initial safety checks shall include:
-That capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking;
-That there no live electrical components and wiring are exposed while charging, recovering or purging the
system;
-That there is continuity of earth bonding.
17. Repairs to sealed components
1. During repairs to sealed components, all electrical supplies shall be disconnected from the equipment
being worked upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an electrical
supply to equipment during servicing, then a permanently operating form of leak detection shall be located at
the most critical point to warn of a potentially hazardous situation.
2. Particular attention shall be paid to the following to ensure that by working on electrical components, the
casing is not altered in such a way that the level of protection is affected. This shall include damage to cables,
excessive number of connections, terminals not made to original specification, damage to seals, incorrect
fitting of glands, etc.
Ensure that apparatus is mounted securely.
Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of
preventing the ingress of flammable atmospheres. Replacement parts shall be in accordance with the
manufacturer’s specifications.
NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment.
Intrinsically safe components do not have to be isolated prior to working on them.
18. Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not
exceed the permissible voltage and current permitted for the equipment in use.
Intrinsically safe components are the only types that can be worked on while live in the presence of a
flammable atmosphere. The test apparatus shall be at the correct rating.
Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of
refrigerant in the atmosphere from a leak.
19. Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any
other adverse environmental effects. The check shall also take into account the effects of aging or continual
vibration from sources such as compressors or fans.
20. Detection of flammable refrigerants
Under no circumstances shall potential sources of ignition be used in the searching for or detection of
refrigerant leaks. Ahalide torch (or any other detector using a naked flame) shall not be used.
21. Leak detection methods
The following leak detection methods are deemed acceptable for systems containing flammable refrigerants.
Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not be
adequate, or may need re-calibration. (Detection equipment shall be calibrated in a refrigerant-free area.)
Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak
detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the
refrigerant employed and the appropriate percentage of gas (25 % maximum) is confirmed.
Leak detection fluids are suitable for use with most refrigerants but the use of detergents containing chlorine
shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work.
If a leak is suspected, all naked flames shall be removed/ extinguished.
If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the
system, or isolated (by means of shut off valves) in a part of the system remote from the leak. Oxygen free
nitrogen (OFN) shall then be purged through the system both before and during the brazing process.
22. Removal and evacuation
When breaking into the refrigerant circuit to make repairs or for any other purpose conventional procedures
shall be used. However, it is important that best practice is followed since flammability is a consideration. The
following procedure shall be adhered to:
- Remove refrigerant;
- Purge the circuit with inert gas;
- Evacuate;
16
ENG
- Purge again with inert gas;
-Open the circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be flushed
with OFN to render the unit safe. This process may need to be repeated several times. Compressed air or
oxygen shall not be used for this task.
Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the
working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. This process
shall be repeated until no refrigerant is within the system. When the final OFN charge is used, the system shall
be vented down to atmospheric pressure to enable work to take place. This operation is absolutely vital if
brazing operations on the pipe-work are to take place.
Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is ventilation
available.
23. Decommissioning
Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment
and all its detail. It is recommended good practice that all refrigerants are recovered safely. Prior to the task
being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of
reclaimed refrigerant. It is essential that electrical power is available before the task is commenced.
a. Become familiar with the equipment and its operation.
b. Isolate system electrically.
c. Before attempting the procedure, ensure that:
- mechanical handling equipment is available, if required, for handling refrigerant cylinders;
- all personal protective equipment is available and being used correctly;
- the recovery process is supervised at all times by a competent person;
- recovery equipment and cylinders conform to the appropriate standards.
d. Pump down refrigerant system, if possible.
e. If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the
system.
f. Make sure that cylinder is situated on the scales before recovery takes place.
g. Start the recovery machine and operate in accordance with manufacturer’s instructions.
h. Do not overfill cylinders. (No more than 80 % volume liquid charge).
i. Do not exceed the maximum working pressure of the cylinder, even temporarily.
j. When the cylinders have been filled correctly and the process completed, make sure that the cylinders and
the equipment are removed from site promptly and all isolation valves onthe equipment are closed off.
k. Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and
checked.
24. Labelling
Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label
shall be dated and signed. Ensure that there are labels on the equipment stating the equipment contains
flammable refrigerant.
25. Recovery
When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good
practice that all refrigerants are removed safely.
When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are
employed. Ensure that the correct number of cylinders for holding the total system charge are available. All
cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i.e. special
cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure-relief valve and associated
shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before
recovery occurs.
The recovery equipment shall be in good working order with a set of instructions concerning the equipment
that is at hand and shall be suitable for the recovery of all appropriate refrigerants including, when applicable,
flammable refrigerants. In addition, a set of calibrated weighing scales shall be available and in good working
order. Hoses shall be complete with leak-free disconnect couplings and in good condition. Before using the
recovery machine, check that it is in satisfactory working order, has been properly maintained and that any
associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult
manufacturer if in doubt.
The recovered refrigerant shall be returned to the refrigerant supplier in the correct recover cylinder, and the
relevant waste transfer note arranged. Do not mix refrigerants in recovery units and especially not in cylinders.
If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable
level to make certain that flammable refrigerant does not remain within the lubricant. The evacuation process
shall be carried out prior to returning the compressor to the suppliers. Only electric heating to the compressor
body shall be employed to accelerate this process. When oil is drained from a system, it shall be carried out
safely.
17
ENGENG
INSTALLATION PRECAUTIONS (R32)
Important considerations
1. The air conditioner you buy must be installed by professional personnel and the Installation manual is used
only for the professional installation personnel! The installation specifications should be subject to our after-
sale service regulations.
2. When filling the combustible refrigerant, any of your rude operations may cause serious injury or injuries to
human body or bodies and object or objects.
3. A leak test must be done after the installation is completed.
4. It is a must to do the safety inspection before maintaining or repairing an air conditioner using combustible
refrigerant in order to ensure that the fire risk is reduced to minimum.
5. It is necessary to operate the machine under a controlled procedure in order to ensure that any risk arising
from the combustible gas or vapor during the operation is reduced to minimum.
6. Requirements for the total weight of filled refrigerant and the area of a room to be equipped with an air
conditioner (are shown as in the following Tables GG.1 and GG.2)
The maximum charge and the required minimum floor area
m1 = (4 m3) x LFL , m2 = (26 m3) x LFL, m3 = (130 m3 ) x LFL
Where LFL is the lower flammable limit in kg/m3, R32 LFL is 0.038 kg/m3.
For the appliances with a charge amount m1 < M = m2:
The maximum charge in a room shall be in accordance with the following:
mmax = 2.5 x (LFL)(5/4) x h0 x (A)1/2
The required minimum floor area Amin to install an appliance with refrigerant charge M (kg) shall be in accordance
with following: Amin = (M/ (2.5 x (LFL)(5/4) x h0))2
Where:
Category LFL
(kg/m3)h0 (m) Floor area (m2)
4 7 10 15 20 30 50
R32 0.306
11.14 1.51 1.8 2.2 2.54 3.12 4.02
1.8 2.05 2.71 3.24 3.97 4.58 5.61 7.254
2.2 2.5 3.31 3.96 4.85 5.6 6.86 8.85
Table GG.1 - Maximum charge (kg)
Category LFL
(kg/m3)h0 (m) Charge amount (M) (kg) Minimum room area (m2)
4 7 10 15 20 30 50
R32 0.306
1.224kg 1.836kg 2.448kg 3.672kg 4.896kg 6.12kg 7.956kg
0.6 29 51 116 206 321 543
110 19 42 74 116 196
1.8 3 6 13 23 36 60
2.2 24915 24 40
Table GG.2 - Minimum room area (m2)
18
ENG
Installation Safety Principles
1. Site Safety
2. Operation Safety
3. Installation Safety
Open Flames Prohibited
Ventilation Necessary
Mind Static Electricity
Must wear protective clothing and anti-static gloves
Don`t use mobile phone
Refrigerant Leak Detector
Appropriate Installation Location
Please note that:
1. The installation site should be well-ventilated.
2. The sites for installing and maintaining an air conditioner using Refrigerant R32 should be free from open fire
or welding, smoking, drying oven or any other heat source higher than 548 which easily produces open fire.
3. When installing an air conditioner, it is necessary to take appropriate anti-static measures such as wear anti-
static clothing and/or gloves.
4. It is necessary to choose the site convenient for installation or maintenance wherein the air inlets and outlets
of the indoor and outdoor units should be not surrounded by obstacles or close to any heat source or
combustible and/or explosive environment.
5. If the indoor unit suffers refrigerant leak during the installation, it is necessary to immediately turn off the valve
of the outdoor unit and all the personnel should go out till the refrigerant leaks completely for 15 minutes. If
the product is damaged, it is a must to carry such damaged product back to the maintenance station and it is
prohibited to weld the refrigerant pipe or conduct other operations on the user’s site.
6. It is necessary to choose the place where the inlet and outlet air of the indoor unit is even.
7. It is necessary to avoid the places where there are other electrical products, power switch plugs and sockets,
kitchen cabinet, bed, sofa and other valuables right under the lines on two sides of the indoor unit.
The left picture is the schematic diagram
of a refrigerant leak detector.
19
ENG
Suggested Tools
Tool Picture Tool Picture Tool Picture
Standard
Wrench Pipe Cutter Vacuum Pump
Adjustable/
Crescent
Wrench
Screw drivers
(Phillips & Flat
blade)
Safety Glasses
Torque Wrench Manifold and
Gauges Work Gloves
Hex Keys or
Allen Wrenches Level Refrigerant
Scale
Drill & Drill Bits Flaring tool Micron Gauge
Hole Saw Clamp on Amp
Meter
Inverter Models Capacity (Btu/h) 9K-12K 18K-36K
Lenght of pipe with standard charge 5m 5m 5m 5m
Lenght of pipe with standard charge (Like: North
American, etc.) 7.5m 7.5m 7.5m 7.5m
Maximum distance between indoor and outdoor unit 15m 25m 25m 25m
Additional refrigerant charge 20g/m 15g/m 30g/m 25g/m
Max. diff. in level between indoor and outdoor unit 10m 10m 10m 10m
Type of refrigerant R22/R410A R32 R22/R410A R32
Pipe Length and Additional Refrigerant
PIPE Newton meter [N x m] Pound-force foot (1bf-ft) Kilogram-force meter
(kgf-m)
1/4" (ɸ6) 18 - 20 24.4 - 27.1 2.4 - 2.7
3/8” (ɸ9.52) 30 - 35 40.6 - 47.4 4.1 - 4.8
1/2” (ɸ12) 45 - 50 61.0 - 67.7 6.2 - 6.9
5/8” (ɸ15.88) 60 - 65 81.3 - 88.1 8.2 - 8.9
Torque Parameters
20
ENG
This table is only for reference, the installation shall meet the requirements of local laws
and regulations.
NOTE
Maximum Operating
Current of Air
Conditioner (A)
Minimum Wire Cross-
sectional Area (mm2)
Specification of Socket
or Switch (A) Fuse Specification (A)
≤ 8 0.75 10 20
> 8 and ≤10 1.0 10 20
> 10 and ≤15 1.5 16 32
> 15 and ≤24 2.5 25 32
> 24 and ≤28 4.0 32 64
> 28 and ≤32 6.0 40 64
Dedicated Distribution Device and Wire for Air Conditioner
Step1: Select Installation location
1. Ensure the installation complies with the installation minimum dimensions (defined below) and meets the
minimum and maximum connecting piping length and maximum change in elevation as defined in the
System Requirements section.
2. Air inlet and outlet will be clear of obstructions, ensuring proper airflow throughout the room.
3. Condensate can be easily and safely drained.
4. All connections can be easily made to outdoor unit.
5. Indoor unit is out of reach of children.
6. A mounting wall strong enough to withstand four times the full weight and vibration of the unit.
7. Filter can be easily accessed for cleaning.
8. Leave enough free space to allow access for routine maintenance.
9. Install at least 10 ft. (3 m) away from the antenna of TV set or radio. Operation of the air conditioner may
interfere with radio or TV reception in areas where reception is weak. An amplifier may be required for the
affected device.
10. Do not install in a laundry room or by a swimming pool due to the corrosive environment.
INDOOR UNIT INSTALLATION
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190
  • Page 191 191
  • Page 192 192
  • Page 193 193
  • Page 194 194
  • Page 195 195
  • Page 196 196
  • Page 197 197
  • Page 198 198
  • Page 199 199
  • Page 200 200
  • Page 201 201
  • Page 202 202
  • Page 203 203
  • Page 204 204
  • Page 205 205
  • Page 206 206
  • Page 207 207
  • Page 208 208
  • Page 209 209
  • Page 210 210
  • Page 211 211
  • Page 212 212
  • Page 213 213
  • Page 214 214
  • Page 215 215
  • Page 216 216
  • Page 217 217
  • Page 218 218
  • Page 219 219
  • Page 220 220
  • Page 221 221
  • Page 222 222
  • Page 223 223
  • Page 224 224
  • Page 225 225
  • Page 226 226
  • Page 227 227
  • Page 228 228
  • Page 229 229
  • Page 230 230
  • Page 231 231
  • Page 232 232
  • Page 233 233
  • Page 234 234
  • Page 235 235
  • Page 236 236
  • Page 237 237
  • Page 238 238
  • Page 239 239
  • Page 240 240
  • Page 241 241
  • Page 242 242
  • Page 243 243
  • Page 244 244
  • Page 245 245
  • Page 246 246
  • Page 247 247
  • Page 248 248
  • Page 249 249
  • Page 250 250
  • Page 251 251
  • Page 252 252
  • Page 253 253
  • Page 254 254
  • Page 255 255
  • Page 256 256
  • Page 257 257
  • Page 258 258
  • Page 259 259
  • Page 260 260
  • Page 261 261
  • Page 262 262
  • Page 263 263
  • Page 264 264
  • Page 265 265
  • Page 266 266
  • Page 267 267
  • Page 268 268
  • Page 269 269
  • Page 270 270
  • Page 271 271
  • Page 272 272
  • Page 273 273
  • Page 274 274
  • Page 275 275
  • Page 276 276
  • Page 277 277
  • Page 278 278
  • Page 279 279
  • Page 280 280
  • Page 281 281
  • Page 282 282
  • Page 283 283
  • Page 284 284
  • Page 285 285
  • Page 286 286
  • Page 287 287
  • Page 288 288
  • Page 289 289
  • Page 290 290
  • Page 291 291
  • Page 292 292
  • Page 293 293
  • Page 294 294
  • Page 295 295
  • Page 296 296
  • Page 297 297
  • Page 298 298
  • Page 299 299
  • Page 300 300
  • Page 301 301
  • Page 302 302
  • Page 303 303
  • Page 304 304
  • Page 305 305
  • Page 306 306
  • Page 307 307
  • Page 308 308
  • Page 309 309
  • Page 310 310
  • Page 311 311
  • Page 312 312
  • Page 313 313
  • Page 314 314
  • Page 315 315
  • Page 316 316
  • Page 317 317
  • Page 318 318
  • Page 319 319
  • Page 320 320
  • Page 321 321
  • Page 322 322
  • Page 323 323
  • Page 324 324
  • Page 325 325
  • Page 326 326
  • Page 327 327
  • Page 328 328
  • Page 329 329
  • Page 330 330
  • Page 331 331
  • Page 332 332
  • Page 333 333
  • Page 334 334
  • Page 335 335
  • Page 336 336
  • Page 337 337
  • Page 338 338
  • Page 339 339
  • Page 340 340
  • Page 341 341
  • Page 342 342
  • Page 343 343
  • Page 344 344
  • Page 345 345
  • Page 346 346
  • Page 347 347
  • Page 348 348
  • Page 349 349
  • Page 350 350

Tesla TT34TP21-1232IAW Manual de utilizare

Categorie
Aparate de aer condiționat cu sistem divizat
Tip
Manual de utilizare